TRICONEX 7400212-100 Safety I/O Module

Installing a Fanned-Out Cable

This procedure explains how to install a fanned-out cable.

Procedure

1 Set up the Tricon chassis and install the I/O modules as described in the Planning and

Installation Guide for Tricon v9–v10 Systems.

2 Remove incoming power from the Tricon system (optional).

3 Re-key the female connector on the fanned-out cable to match the male connector on the

Tricon backplane. For instructions, see Appendix A, Re-Keying Connectors.

4 Attach the fanned-out cable connector to the panel connector that is above the

corresponding I/O module.

5 Connect the fanned-out cable wires to the field devices or marshaling termination.

6 Perform a static check of the wiring.

7 If Tricon power was removed in step 1. restore power to the Tricon system.

8 Apply field power to the devices connected to the fanned out cable.

9 Verify the connection of all I/O points to the appropriate field wiring by using the

TriStation software to inspect input points and force output points.

Note To inspect input points and force output points, see the Planning and Installation

Guide for Tricon v9–v10 Systems.

10 Load and test the control program using TriStation.

If you need additional information on how to install fanned-out cables, contact the IPS Global

Client Support (GCS) center.

Removing or Replacing a Fanned-Out Cable

This procedure explains how to remove or replace a fanned-out cable.

Procedure

1 Remove field power from the termination panel.

2 Detach the fanned-out cable connector that is above the corresponding I/O module.

3 Detach the fanned-out wires from the field termination panel or the field devices

16-Point Commoned Digital Input Term Panels

This section describes 16-point commoned digital input term panels. Model numbers of these

term panels are:

• 9561-810 (115 V, commoned, 16 pts.)

• 9562-810 (48 V, commoned, 16 pts.)

• 9563-810 (24 V, commoned, 16 pts.)

• 9563-910 (24 V, commoned, resistor protected, 16 pts.)

This figure represents a typical 16-point commoned digital input termination panel with fuses

and blown-fuse indicators.