CTI

CTI  2531 32-Point Form-A Relay Output Module

2531 32-Point Form-A Relay Output Module

The 2531 module provides 32 Form-A relay outputs for the 2500 Series® I/O base.

The module uses relay output circuits to switch on or off external devices such as pilot lamps, motor starters, or solenoids. The 2531 is designed to switch externally supplied 15 to 240 VAC and 15 to 30 VDC.

Features

Replaces Siemens® 505-4932-A with no rewiring

32 Form-A relay outputs

Isolated 1500V group-to-group

Isolation in groups of 8

Individually fused outputs

4.0 Amps per output

Description

2500 Series®  PLC System

The 2531 32-Point Form-A Relay Output Module

provides 16 or 32 Form-A outputs isolated in

groups of eight for the CTI 2500 Series® or

Simatic® 505 I/O base. The module uses relay

output circuits to switch on or off external devices

such as pilot lamps, motor starters, or solenoids.

The 2531 is designed to switch externally

supplied 15 to 240 VAC and 15 to 30 VDC. The

internal logic signals are isolated from the

external outputs to 2100 VDC.

Specifications

Outputs per module: 16 or 32

Isolation: 2100 VDC channel-to-backplane

3000 VDC group-to-group

Output voltage: 15 – 240 VAC

15 – 30 VDC

Indicators: 32 individual LEDs

Maximum output current:

4A per point (resistive)

8A per group (resistive)

Switching rate: 5 ops/sec (no load),

0.5 ops/sec (rated load)

Type of contact: Form A

Type of outputs: Individually fused

Minimum contact load: 10mA @ 5 VDC

Contact life:

@ full rated current, 4A = 400.000 cycles

@ 2A = 1.000.000 cycles

Backplane Power: 1.7 Watts

User Power Supply: 24VDC +10%

600 mA (all outputs ON)

Fuses: field replaceable for each channel. The

module uses 32. 5 amp, 250V, 1 amp, 250V,

Littelfuse #215.005 Littelfuse #217.001

Schurter #0001.2511 Schurter #034.1516

Features

• CTI 2500 Series® or Simatic® 505 base format

• 16 or 32 Form A relay outputs

Product Bulletin

• Replaces Siemens® 505-4932 with no rewiring

• Isolated 3000 VDC group-to-group

• Isolation in groups of 8

• Wide 15-240 VAC and 15-30 VDC output range

• 4.0 Amps per output

• Individually fused outputs

Connector: Removable 2500-40F required for new

installations. The connector is ordered separately.

Wire Gauge: 14 – 22 AWG

Module Size: Single-wide

Agency Approvals:

UL, UL-Canada, CE, Class 1 Div 2

Shipping Weight: 1.5 lb. (0.68 Kg)