CTI 2589-B 8/16/32-Point Universal Discrete Input Module

2589-B 8/16/32-Point Universal Discrete Input Module

The 2589-B is designed to accept both AC and DC voltage inputs and is compatible with the CTI 2500 Series® or Simatic® 505 I/O base.

The 2589-B can be configured to login as 8. 16 or 32-points. The 2589-B allows operation of all 32pt at 240VAC, compared to only 16pt which were available on 2589-A.

Features

2589-B replaces CTI 2589-A, Siemens® 505-4008. 4016. 4032. 4116. 4132. 4208. 4216. 4232. 4308. 4316-A, 4332. 4408. 4416-A, 4432-A with no rewiring

Can login as 8. 16. or 32 points

Isolation in groups of 2. 4. or 8 points (depending on configuration)

Wide 11V to 250V AC/DC input range

Description

The 2589-B 8/16/32-Point Universal Discrete Input

Module accepts a wide range of voltage signals. It is

designed to accept both AC and DC voltage allowing

the user to pick and choose ranges on a single

module. The 2589-B can be configured as an 8-point,

16-point, or 32-point module and can replace many

Siemens® input products with no rewiring. Motor

centers, optical sensors, limit switches and utility

control are excellent examples of applications for this

product.

Features

• CTI 2500 Series® or Simatic® 505 base format

• 8. 16. or 32 universal input points

• Replaces Siemens® 505-4008-A, 4016-A, 4032-A,

4208-A, 4216-A, 4232-A, 4308. 4316. 4316-A, 4332.

4408-A, 4416-A, 4432-A with no rewiring

• 1500V channel-to-PLC backplane and group-to

group isolation

• Wide 11V to 220V AC/DC range (selectable by

group)

• Isolation in groups of 4 or 8 (selectable on 2589-B)

• Sourcing or sinking inputs

• Single-wide module

The 2589-B was designed to be primarily a 32pt module. However, in order to provide maximum flexibility for the user, it

may be configured as an 8 or 16 point module. Some details below to help the user better understand the jumper

settings and labeling discrepancies for settings other than 32 points.

16 Point Mode: Move jumper in “Login” box to location

JP130 to choose 16pt mode. Ensure the Isolation

jumpers J3-6 are in Enhanced positions to correspond

to the Siemens® 16 point modules (4 inputs/

common); otherwise two 18 or 20 ga. jumper wires

from AR to BR and CR to DR on the front panel

connector are needed (see Figures, pg 2) to allow for

8 inputs/common. Also, note that many of the printed

channels (CH 1-CH 32) on the PC board are no

longer valid, nor are the front panel connector labels,

or the LED channel indicators. (You may find it helpful

to manually relabel the connector in the space

provided for the 16 Point Login option.) If 16 Point is

enabled, the following table’s 16pt. row is the new

correlation of PC board and connector label printing.

For example, in 16 Point Login Configuration, the

board marking for channel 10 (CH 10) would be the

input channel 6. Likewise, the PC board marking for

CH 28 would correlate to input channel 16.