CTI 2585 16-Point TTL/Word Input Module
2585 16-Point TTL/Word Input Module
The 2585 16-point isolated TTL input module accepts sixteen TTL inputs to the CTI 2500 Series® or Simatic® 505 I/O base.
Features
Selectable discrete (X) or word (WX) format
1500 VDC channel-to-backplane isolation
Sourcing and sinking applications
Indicator LEDs for each channel
Specifications
Inputs per module: 16
Isolation:
500 VDC channel-to-channel
1500 VDC channel-to-backplane
Input Voltage:
2.6 to 28 VDC
TTL OFF <0.8 VDC TTL ON > 2.6 VDC
1500 VDC channel-to-backplane
Input Current:
20 mA max. per circuit (0.5 mA @ 2.6 VDC)
Isolation:1500 VDC channel-to-backplane
Turn ON Time: Approx. 1 mSec nominal
Turn OFF Time: Approx. 2 mSec nominal PLC
Reporting: X or WX (jumper selectable)
Wire gauge: 14-22 AWG removable connectors
Backplane power: 1.4 Watts (all outputs active)
Module size: Single-wide
Blown fuse indication: Front panel LED
Shipping Weight: 1.5 lb. (0.68 Kg)
Additional Product Information:
On CTI’s Website you find will links to the 2500
Series Std Environmental Specifications and the UL
Agency Certificates of Compliance
Description
The 2585 16-Point TTL Input Module accepts sixteen
TTL driven inputs to the CTI 2500 SeriesTM or
Simatic® 505 Series I/O base. The inputs are
isolated channel-to-channel.
The 2585 has an input voltage range from 2.6 to 28
VDC; therefore, the inputs may be driven by CMOS
and open collector transistor devices.
Features
• CTI 2500 Series and Simatic 505 base format
• 500 V channel-to-channel isolation
• 1500 V channel-to-PLC backplane isolation
Word and Discrete Mode
The 2585 may operate as a 16 Bit Word Input Module or as a 16 Dis
crete Input Module. By setting JP1 in Word Mode and using Workshop
to configure I/O the 2585 will look like a standard WX input module; for
example WX1-WX8.
NOTE: The 2585 will be mapped as the first WX address (i.e. WX1). In
Word Mode Channel 1 corresponds to bit 16 or LSB and Channel 16
corresponds to Bit 1 or MSB.
I/O MODULE DEFINITION FOR CHANNEL 1 BASE 00
I/O
SLOT ADDRESS
NUMBER OF BIT AND WORD I/O SPECIAL
Figure 1 I/O Word Mode Configuration Chart
In the example Figure 2. the 16-point TTL input module is inserted
in slot 1 in I/O base 0 and configured as a DISCRETE module using
JP1. In the example below data appears as 16 “X” locations starting
at “X1”. For your particular module, look in the chart for the number
corresponding to the slot occupied by the module. If bit locations
appear on this line, then the module is registered in the PLC
memory and the module is ready for operation.