ICS Triplex

ICS TRIPLEX TC-801-02-4M5 Controller Module Card

The module has a Power PC Processor. Bootstrap software is stored on Erasable

Programmable Read Only Memory (EPROM). Operational firmware is stored in flash memory

and may be upgraded via the Front Panel Port.

The Trusted Operating System is used on both the TMR Processor and CI. The real time

kernel is a high speed, high functionality kernel made for fault tolerant distributed systems.

The kernel provides basic services (such as memory management) and interference free

software environments.

A module watchdog monitors processor operation and the power supply unit (PSU) output

voltages.

The module is supplied with a dual redundant +24 Vdc power feed from the chassis

backplane. An on-board power supply unit provides voltage conversion, supply conditioning

and protection.

The Trusted CI communicates with the Trusted TMR Processor via the triplicated Inter

Module Bus. When polled by the Trusted TMR Processor, the module’s bus interface votes

the data 2 out of 3 (2oo3) from the Inter-Module Bus and transmits back its reply via all

three Inter-Module Bus channels. The remainder of the Communications Interface is

simplex.

B&R X20DO9322
ABB ACS880-01-361A-5
ABB PC D530 A102 3BHE041343R0102
ABB OBIC0100-24VDC
Foxboro 43AP-FA42D/PB-AA
SAMSUNG SPDI-24
SAMSUNG RSPC X32
ICS Triplex T8270
ICS Triplex T8300
ICS Triplex T8123
ICS Triplex T8191
ICS Triplex T8225
ICS Triplex T8110B
ICS Triplex T8151B
ICS Triplex T8153
ICS Triplex T8310

All communications transceivers are electrically isolated from each other and the module

and have additional transient protection measures.

The module internal supplies are isolated from the dual 24 Vdc feeds.

Communications

Data is transferred between the TMR Processor and the Communications Interfaces using a

common interface called the Network Variable Manager. When data is read from a Trusted

System, the data is obtained from the local copy maintained on the Communications

Interface, providing a fast response.

Data writes are more complicated. If a data write simply updated the local copy and was

then relayed to the processor, the other Communications Interfaces in the system would

carry different data. This may cause problems for redundant links.

To overcome this problem, when data is written to a Communications Interface, it is first

passed to the TMR Processor and the write is acknowledged immediately by the

发表回复