The Trusted® TMR 24 Vdc Digital Input module interfaces to 40 field input

devices. Fault tolerance is achieved through a Triple Modular Redundant

(TMR) architecture within the module for each of the 40 input channels.

Each field input is triplicated and the input voltage is measured using a

sigma-delta input circuit. The resulting field voltage measurement is

compared to user configurable threshold voltages to determine the reported

field input state. When a line-monitoring device is installed at the field switch,

the module can detect open and short circuit field cables. Line monitoring

functions are independently configured for each input channel.

The triplicated voltage measurement, coupled with onboard diagnostic testing,

provides comprehensive fault detection and tolerance.

The module provides onboard Sequence of Events (SOE) reporting with a

resolution of 1 ms. A change of state triggers an SOE entry. States are

determined by voltage thresholds that can be configured on a per channel

ABB 3BHE021889R0101
ABB 1KGT022300R0001 560BCU04
ABB 1KGT022111R42
ABB HIEE300888R0002 UA C389 AE02
ABB 3BHL000253P0002
ABB 3BHL001862P0001
ABB 58926451升级68262747
GE IS420UCSBH1A
GE DS3800HSQE 1H1H
ABB 3BHB006716R0277 (SYN 5302a-Z, V277)
A-B 80026-529-01
GE 369-HI-R-M-0-0-0-E
BentlyNevada 102044-00-18-10-02
BentlyNevada 102045-040-00
BentlyNevada 102046-50

Data is transferred between the TMR Processor and the Communications Interfaces using a

common interface called the Network Variable Manager. When data is read from a Trusted

System, the data is obtained from the local copy maintained on the Communications

Interface, providing a fast response.

Data writes are more complicated. If a data write simply updated the local copy and was

then relayed to the processor, the other Communications Interfaces in the system would

carry different data. This may cause problems for redundant links.

To overcome this problem, when data is written to a Communications Interface, it is first

passed to the TMR Processor and the write is acknowledged immediately by the

Communications Interface (to avoid communications delays). The processor updates its own

database and then sends the data back to all Communications Interfaces so that they all

have the same data. This can take one or two application scans. This means that subsequent

reads will receive the old data immediately after the write, until the new data has been

distributed.

All changes to CI parameters (.ini changes) loaded online do not require a power cycle, and

will take effect immediately. The Communications Interface disconnects all communications

and restarts. Communications is also restarted on an application online update and is shut

down when the application is stopped.

The Trusted® Processor is the main processing component in a Trusted System. It is a powerful,

user-configurable module providing overall system control and monitoring facilities and processes

input and output data received from a variety of analogue and digital Input / Output (I/O) modules

across a Trusted TMR Inter-Module Communications Bus.

The range of applications for the Trusted TMR Processor vary in integrity level and include fire and

gas control, emergency shutdown, monitoring and control, and turbine control.