SAMSUNG

Samsung SSAS21-RTD Resistance Temperature Detector Input Module

Samsung SSAS21-RTD Resistance Temperature Detector Input Module is a high-precision thermal measurement interface designed for the Samsung SSAS21 programmable logic controller (PLC) system. Engineered for multi-channel process monitoring, it directly converts low-resistance signals from field RTD sensors into digital temperature data for real-time CPU processing without requiring external signal converters.

Technical Parameter List

Parameter Specification
Model Code SSAS21-RTD
Series Samsung SSAS21 Automation Platform
Supported Sensors Pt100, Pt1000, Cu50, Cu100 (2-wire, 3-wire, 4-wire)
Input Channels 4 / 8 Channels per Module
Temperature Range -200°C to +850°C (Pt100 dependent)
Conversion Resolution 16-bit Sigma-Delta ADC
Measurement Accuracy ±0.1% of Full Scale (±0.2°C at 25°C ambient)
Isolation Rating Photocoupler Isolation (1500V AC between channel and backplane)
Conversion Speed 20 ms to 100 ms per channel (configurable)
Internal Power Draw Powered via SSAS21 backplane 5V DC bus

Core Advantages & Product Features

Direct Sensor Connection: Accepts 2. 3. and 4-wire RTD wiring directly, eliminating the need for costly external temperature transmitters.

Lead Wire Resistance Compensation: 3-wire and 4-wire support automatically cancels out line resistance variations over long field cable distances.

High-Precision 16-bit ADC: Delivers high thermal resolution necessary for tight temperature control loops in critical manufacturing processes.

Built-in Channel Isolation: Optoelectronic barriers protect backplane logic from high-voltage field spikes, ground loops, and electrical noise.

Wire-Break & Burnout Diagnostics: Instantly detects broken sensor wires or short circuits, sending automatic error flags to the PLC CPU.

Model Classification

SSAS21-RTD: RTD Resistance Temperature Measurement Input Module.

SSAS21-TC: Thermocouple Temperature Input Module (Millivolt sensor interface).

SSAS21-AI: Standard Analog Input Module (4–20 mA / 0–10 V DC signals).

SSAS21-AO: Standard Analog Output Module (Proportional valve and drive commands).

SSAS21-CPU: Central Processing Unit Module.

Environmental Tolerance Conditions

Operating Temperature: 0°C to +55°C (32°F to 131°F)

Storage Temperature: -25°C to +70°C (-13°F to 158°F)

Operating Relative Humidity: 5% to 95% RH (Non-condensing)

Vibration Immunity: Conforms to IEC 60068-2-6 (10–57 Hz @ 0.075 mm; 57–150 Hz @ 1.0g)

Shock Immunity: 15g peak acceleration, 11 ms duration

Enclosure Protection: IP20 (Requires mounting inside an IP54 or higher control enclosure)

Installation Method

Safety Isolation: Power down the SSAS21 base chassis before installing or removing modules.

Rack Insertion: Align the guide rails on the SSAS21-RTD module with the open chassis slot. Push firmly until the backplane multi-pin connector fully seats.

Module Locking: Tighten the upper and lower panel retention screws to secure the module against cabinet vibration.

Sensor Wiring: Wire RTD sensor leads according to the terminal pinout (3-wire setup: connect A, B, and b terminals). Use twisted-shielded copper wire.

Operating Instructions

Sensor Type Selection: Configure the target RTD type (Pt100 vs Pt1000) and wiring format (3-wire/4-wire) in the SSAS21 PLC programming software before running logic.

Shielding Practice: Ground the overall cable shield braid at the panel enclosure earth ground only to prevent ground potential loops.

Thermal Stabilization: Allow the module to run for 15 minutes after initial power-on to reach internal thermal equilibrium for optimal measurement accuracy.