SAMSUNG

SAMSUNG SMCOM-08 Communication Expansion Card

SAMSUNG SMCOM-08 Communication Expansion Card

The SAMSUNG SMCOM-08 is a dedicated serial communication expansion card engineered for Samsung SPC and SM-series PLC systems. It expands the host controller’s networking capabilities by providing 8 independent serial communication ports (RS-232C / RS-422 / RS-485 configurable). The module enables seamless data exchange between the central PLC and peripheral field devices such as HMIs, variable frequency drives (VFDs), barcode scanners, smart meters, and third-party controllers.

Technical Table

Parameter Specification
Model SAMSUNG SMCOM-08
Communication Ports 8 independent serial channels
Interface Standard Software/Hardware configurable RS-232C / RS-422 / RS-485
Baud Rate 300 bps to 115.2 kbps per channel
Supported Protocols Modbus RTU / ASCII, Samsung Master/Slave Protocol, User-defined serial protocols
Transmission Distance RS-232C: Up to 15 m; RS-422/RS-485: Up to 1200 m (with termination resistor)
Isolation Optocoupler isolation (1500V DC between field side and PLC backplane)
Power Consumption Max 5V DC / 450mA (supplied via PLC backplane bus)
Connector Type Terminal blocks / RJ45 / DB9 (model variant dependent)

Environmental Tolerance Conditions

Operating Temperature: 0°C to +55°C (32°F to 131°F)

Relative Humidity: 5% to 95% RH (non-condensing)

Vibration Resistance: IEC 60068-2-6 compliant (10–57 Hz @ 0.075 mm amplitude, 57–150 Hz @ 1g)

Shock Resistance: IEC 60068-2-27 compliant (15g peak acceleration, 11 ms duration)

Noise Immunity: IEC 61000-4-4 (FTB) 2kV power lines / 1kV signal lines; ESD protection up to 8kV air discharge

Operating Environment: Free from corrosive gases, conductive dust, and direct sunlight

Operating Instructions

Hardware Setup:

Ensure power to the PLC rack is completely isolated.

Seat the SMCOM-08 firmly into the designated expansion slot on the baseplate and lock the retaining clip.

Attach matching 120 Ω termination resistors at both ends of the trunk for long-distance RS-485 networks.

Software Configuration:

Open the Samsung PLC programming environment (e.g., WinGPC).

Map the SMCOM-08 slot address in the I/O table.

Set communication parameters (Baud rate, Data bits, Stop bits, Parity) for each channel to match connected slave devices.

Data Exchange:

Utilize built-in read/write communication functions or memory mapping instructions in ladder logic to initiate polling cycles.

Fault Diagnosis

Indicator / Symptom Possible Cause Corrective Action
RUN LED Off Loose backplane seating or baseplate power supply failure. Re-seat module into slot; check main 24V DC / 5V DC rack power supply.
ERR / FAULT LED On Parameter mismatch or internal checksum error. Check baud rate and frame settings in software; reload configuration to PLC.
TX/RX LED Inactive Wiring polarity reversed or line break. Verify signal wires (TX+/TX-, RX+/RX- or A/B); test continuity with a multimeter.
Intermittent Comm Failures Electromagnetic interference (EMI) or ground potential difference. Use shielded twisted-pair cables; connect cable shield to ground at one end only.

Related Models of the Same Series

Model Description Primary Application
SMCOM-02 / 04 2 / 4-Channel Serial Communication Card Compact serial network expansion
SMETH-01 Industrial Ethernet Module Modbus TCP / EtherNet/IP host communication
SMCU-CPU Main Controller CPU Central processing unit for Samsung SPC/SM PLCs
SMAD-8 Analog Input Module 8-Channel multi-range analog signal processing
SMDA-4 Analog Output Module 4-Channel voltage/current signal output control

Storage Conditions

Storage Temperature: -25°C to +70°C (-13°F to 158°F)

Storage Humidity: 5% to 95% RH (non-condensing)

Packaging: Keep in original anti-static packaging until installation to prevent ESD damage.

Storage Environment: Store in a dry, clean warehouse free from aggressive chemicals, moisture, and mechanical vibration.