VIBRO-METER

Vibro-Meter Relay expansion  RLC16 Mk2    600-045

Relay expansion  RLC16 Mk2    600-045

DESCRIPTION (continued)

The CPUMMk2 + IOCNMk2 rack controller and

communications interface module is an optional

module used to provide additional VM600Mk2 system

functionality such as fieldbus communications

(Modbus TCP and/or PROFIBUS DP); module data

aggregation, processing and sharing; fieldbus

(module-level) and/or module (rack-level)

communications redundancy; front-panel alarm reset

(AR); MPS rack (CPUx) security; system event and

measurement event logging.

VM600Mk2 rack-based monitoring systems

complement the VibroSmart ® distributed monitoring

systems that are also available from Parker Meggitt’s

vibro-meter ® product line, and are compatible with

the same VibroSight ® machinery monitoring

software suite.

CPUMMk2 +  IOCNMk2 modules and

VM600Mk2 racks

The CPUMMk2 + IOCNMk2 rack controller and

communications interface module is used as part of a

VM600Mk2 rack-based monitoring system.

The CPUMMk2 module is always used with an

associated IOCNMk2 module as a pair/set of

modules. Both the CPUMMk2 and the IOCNMk2 are

single-width modules that occupy a single VM600Mk2

rack slot (module position). The CPUMMk2 + IOCNMk2

module can only be used in VM600Mk2 system racks

(ABE04x).

When one CPUMMk2 + IOCNMk2 module is installed in

a VM600Mk2 system rack as a standard rack

controller and communications interface (no module

redundancy), the CPUMMk2 is installed in the front of

a VM600Mk2 rack (typically slot 0) and the associated

IOCNMk2 is installed in the rear of the rack (typically

slot 0), in the slot directly behind the CPUMMk2. Each

module connects directly to the rack’s backplane

using two connectors.

IOCN

When two CPUMMk2 + IOCNMk2 modules are installed

in a VM600Mk2 system rack for rack-level

communications redundancy, the “master” module is

typically installed in slots 0 (front and rear) and the

“subordinate” module is typically installed in slots 1

(front and rear).

Note: The CPUMMk2 + IOCNMk2 module is

compatible with all VM600Mk2 system racks (ABE04x)

and later VM600 system racks (ABE04x) with an

I2C interface (VME utility bus)

CPUMMk2 +  IOCNMk2 module functionality

As a fieldbus communications interface for a

VM600Mk2 monitoring system, the CPUMMk2 module

communicates with other VM600Mk2 processing

modules in the rack (such as the MPC4Mk2 and/or

future AMCxMk2 ) via the rack’s VME bus and with

XMx16 modules via a system Ethernet link in order to

obtain measurement data and then share this

information with third-party systems such as a DCS

or PLC.

Note: The CPUMMk2 is not compatible with first

generation VM600Mk1 cards such as the

MPC4 /IOC4T and AMC8 /IOC8T card pairs.

The data shared via fieldbus can be the “raw”

measurement data obtained from MPC4Mk2 or

XMx16 modules, and/or the status (health) data

obtained from the CPUMMk2 modules, or the data

can be further processed as required (defined by the

fieldbus configuration file). For example, the

processing supported includes basic mathematical

functions such as arithmetic and logical operations,

and many other supporting functions.

Note: The CPUMMk2 can be used as a data

communications gateway for XMx16 modules in low

data-bandwidth applications. For example, handling

hundreds of bytes of static data via Modbus TCP and/

or PROFIBUS DP. However, the CPUMMk2 cannot be

used as a gateway for XMx16 modules in high data

bandwidth applications as the dynamic data

(waveforms and spectra) generated by XMx16

modules typically requires a direct connection to the

VibroSight ® software.