Safe Torque Off (STO)

Anadditional digital input (STO) releases the poweroutput stageof thedriveas longas a24V signal is appliedto

this input. If the STO input goes open-circuit, then powerwill nolongerbesuppliedtothemotor, andthedrivewill

lose all torque and coast toastop.

Input STO (X1/3)

—Floating, reference groundis GND

—24V±10%,20mA

ThisinputisnotcompatiblewithIEC61131-2.

Youcanthus achievearestart lock-out forpersonnel safety by usingtheSTOinput inconjunctionwithanexter

nal safety circuit.

Advantages of theSTOfunction:

l TheDCbuslink remains charged, sincethemains supply lineremains active.

l Onlylow voltages areswitched, sothereis nocontact wear.

l Verylittle wiring is required.

TheSTOsafety concept is certified. Thesafety circuit concept usedforthesafety function”SafeTorqueOff” in

the drive is suited for SIL 2accordingtoEN 61800-5-2andPLd/ CAT3accordingtoISO13849-1.

6.17.1 Safety characteristic data

Thesubsystems (AKD)aredescribedwiththefollowingcharacteristic data:

Device

Operation Mode

EN13849-1

EN62061

STO STOsinglechannel

6.17.2 Use as directed

PLd,CAT3 SIL2

PFH[1/h]

SFF[%]

AKD-P00607-NBEC-0000

TheSTOfunctionis exclusively intendedtoprovidesafety forpersonnel by preventingtherestart of asystem.

Toachievethis personnel safety, thewiringof thesafety circuits must meet thesafety requirements of IEC

60204. ISO12100andISO13849.

6.17.3 Prohibited Use

TheSTOfunctionmust not beusedif thedriveis tobemadeinactiveforthefollowingreasons:

1. Cleaning, maintenanceandrepairoperations, longinoperativeperiods. Insuchcases, theentiresystem

should bedisconnectedfrom thesupply andsecured(mainswitch).

2. Emergency-stopsituations. Inanemergency-stopsituation, themaincontactoris switchedoff (by the

emergency-stopbutton).

Enclosure

SincethedrivemeetsIP20.youmustselectanenclosurethatpermitssafeoperationofthedrive.Theenclosure

mustatleastmeetIP54.

6.17.7 Wiring

Ifyouarewiringleadsthatareoutsidethespecifiedenclosure(IP54),thecablesmustbelaiddurably(firmly),pro

tectedfromoutsidedamage(forexample,bylayingthecableinaduct),placedindifferentsheathedcables,or

protectedindividuallybygroundingconnection.

WiringremainingwithinthespecifiedenclosuremustmeettherequirementsofthestandardIEC60204-1.