Kollmorgen AKD-P00607-NBEC-0000 400/480VAC 4.40KVA Servo Drive.
Kollmorgen AKD-P00607-NBEC-0000 400/480VAC 4.40KVA Servo Drive.
Safe Torque Off (STO)
Anadditional digital input (STO) releases the poweroutput stageof thedriveas longas a24V signal is appliedto
this input. If the STO input goes open-circuit, then powerwill nolongerbesuppliedtothemotor, andthedrivewill
lose all torque and coast toastop.
Input STO (X1/3)
—Floating, reference groundis GND
—24V±10%,20mA
ThisinputisnotcompatiblewithIEC61131-2.
Youcanthus achievearestart lock-out forpersonnel safety by usingtheSTOinput inconjunctionwithanexter
nal safety circuit.
Advantages of theSTOfunction:
l TheDCbuslink remains charged, sincethemains supply lineremains active.
l Onlylow voltages areswitched, sothereis nocontact wear.
l Verylittle wiring is required.
TheSTOsafety concept is certified. Thesafety circuit concept usedforthesafety function”SafeTorqueOff” in
the drive is suited for SIL 2accordingtoEN 61800-5-2andPLd/ CAT3accordingtoISO13849-1.
6.17.1 Safety characteristic data
Thesubsystems (AKD)aredescribedwiththefollowingcharacteristic data:
Device
Operation Mode
EN13849-1
EN62061
STO STOsinglechannel
6.17.2 Use as directed
PLd,CAT3 SIL2
PFH[1/h]
SFF[%]

AKD-P00607-NBEC-0000
TheSTOfunctionis exclusively intendedtoprovidesafety forpersonnel by preventingtherestart of asystem.
Toachievethis personnel safety, thewiringof thesafety circuits must meet thesafety requirements of IEC
60204. ISO12100andISO13849.
6.17.3 Prohibited Use
TheSTOfunctionmust not beusedif thedriveis tobemadeinactiveforthefollowingreasons:
1. Cleaning, maintenanceandrepairoperations, longinoperativeperiods. Insuchcases, theentiresystem
should bedisconnectedfrom thesupply andsecured(mainswitch).
2. Emergency-stopsituations. Inanemergency-stopsituation, themaincontactoris switchedoff (by the
emergency-stopbutton).
Enclosure
SincethedrivemeetsIP20.youmustselectanenclosurethatpermitssafeoperationofthedrive.Theenclosure
mustatleastmeetIP54.
6.17.7 Wiring
Ifyouarewiringleadsthatareoutsidethespecifiedenclosure(IP54),thecablesmustbelaiddurably(firmly),pro
tectedfromoutsidedamage(forexample,bylayingthecableinaduct),placedindifferentsheathedcables,or
protectedindividuallybygroundingconnection.
WiringremainingwithinthespecifiedenclosuremustmeettherequirementsofthestandardIEC60204-1.