OMRON CJ1W-SCU21-V1 PLC
OMRON CJ1W-SCU21-V1 PLC
Heater Burnout (HB) Alarm
Item
Maximum heater current
Indication accuracy of input current
Heater burnout alarm setting range
Single-phase AC, 50 A
Specification
±5% of full scale ± 1 digit max.
0.1 to 49.9 A (0.1 A units)
The heater burnout detection function will not operate if the set value is set to 0.0 A or 50.0 A.
(When the SV is 0.0 A, the heather burnout alarm will be OFF. When the SV is 50.0 A, the heater burnout
alarm will be ON.)
Min. detectable ON time *
200 ms
* If the control output is ON for less than 200 ms, the heater burnout detection function will not operate and heater current measurement will not
be performed.
Current Transformer (CT) Ratings
Item
E54-CT1

CJ1W-SCU21-V1
Max. continuous heater current
Dielectric strength
Vibration resistance
Weight
Accessories
50A
1.000 VAC (1 min.)
50 Hz, 98 m/s2
Approx. 11.5 g
None
E54-CT3
120 A *
Approx. 50 g
Contacts (2)
Plugs (2)
Note: Do not use any Current Transformer (CT) other than the OMRON E54-CT1 or E54-CT3 Current Transformer.
* The maximum continuous heater current that can be detected at a CJ1W-TC@@@ Temperature Control Unit is 50 A
Input Specifications
When the Unit is used with CJ-series CPU unit
A switch on the front of the Unit (pin 3 of the DIP switch) selects whether the Temperature Control Unit’s data is stored and indicated as 4-digit
BCD or binary (i.e., 4-digit hexadecimal). Pin 2 of the DIP switch selects whether the temperature is indicated in °C or °F.
The indicated range will be within ±20°C or ±20°F of the setting ranges shown in the following table. *1
Thermocouple Input Setting Ranges
Platinum Resistance Thermometer Input Setting Ranges
Note:When the input type setting switch has been changed, the SV and input compensation values will change as follows:
• If the SV exceeds the setting range, it will be fixed at the lower limit or upper limit of the setting range.
• The position of the decimal point will change if necessary.
For example, when the temperature range is changed by changing the input type setting switch from 0 (K-type thermocouple with a
temperature range of −200 to 1.300°C) to 1 (K-type thermocouple with a temperature range of 0.0 to 500.0°C), an SV of 200°C would be
changed to 20.0°C.
*1. If the allowed indication range is exceeded, a sensor error will occur, the corresponding Sensor Error Flag will be turned ON, and the PV will
contain the data “CCCC.” When a sensor error occurs, that control loop’s control output will be turned OFF. The alarm function will operate
because the PV indicates an abnormally high temperature.
*2. The lower limit for B thermocouple is 0°C or 0°F.
*3. The indicator range for BCD display will be clamped at the lower or upper limit in the region between the lower or upper limit of the setting range
and the point where a sensor error occurs.
When the display units are 0.1°C or 0.1°F, the display’s lower limit value is −99.9 and the upper limit value is 999.9.
No. Input type °C °F
16-bit binary BCD 16-bit binary BCD
| IC693MDL742 GE Series 90-30 component module |
| IC693MDL753H GE Discrete output module |
| IC200ALG326H GE Analog Output module |
| FS-TSDO-0824 HONEYWELL Safe Digital Output FTA |
| FC-USI-0002 HONEYWELL Universal Safety Interface |
| FC-SCDO-0824 HONEYWELL Safe Digital Output FTA |
| FC-SDI-1624 HONEYWELL Safe Digital Output FTA |
| 3500/61-01-01-01 Bently Nevada Temperature Monitor |
| A06B-2082-B403 FANUC AC MOTOR A12/2000 I64 W/BRAKE |
| A06B-2078-B107 FANUC MDL SPM-30 CE APPROVED |
| A06B-6320-H364 FANUC MDL SPM-30 CE APPROVED |
| SDCS-PIN-4 MEASUREMENT CARD ABB |
| SDCS-POW-4-COAT MEASUREMENT CARD ABB |
| SDCS-PIN-51-COAT MEASUREMENT CARD ABB |
| SDCS-PIN-48-COAT MEASUREMENT CARD ABB |
| 2094-AC16-M03-S Allen-Bradley Kinetix 6000 Multi-axis Servo Drives |
| 330104-00-07-10-01-05 Bently Nevada 3300 XL Standard Extension Cable with Armor |