Phoenix QUINT-PS/3AC/24DC/20/CO – Power supply, with protective coating 2320924
QUINT-PS/3AC/24DC/20/CO – Power supply, with protective coating 2320924
Primary-switched power supply unit QUINT POWER, Screw connection, SFB Technology (Selective Fuse Breaking), input:
3-phase, output: 24 V DC / 20 A, adjustable from 18 V DC … 29.5 V DC
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current,
for selective and therefore cost-effective system protection.
In addition, the high system availability is ensured by preventive function monitoring which reports critical operating states before errors can occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST.
Thanks to the adjustable voltage, all ranges between 18 V DC … 29.5 V DC are covered.
AC operation
Nominal input voltage range 3x 400 V AC … 500 V AC
Input voltage range 3x 320 V AC … 575 V AC
2x 360 V AC … 575 V AC
450 V DC … 800 V DC
Voltage type of supply voltage AC
Inrush current < 20 A (typical)
Inrush current integral (I2t) < 3.2 A2s
AC frequency range 45 Hz … 65 Hz
Frequency range DC 0 Hz
Mains buffering time typ. 28 ms (400 V AC)
typ. 43 ms (500 V AC)
Current consumption 3x 1.6 A (400 V AC)
3x 1.3 A (500 V AC)
0.9 A (600 V DC)
Nominal power consumption 783 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Typical response time < 0.16 s

2320924
Permissible backup fuse B6 B10 B16
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 6 A … 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
Efficiency > 93 % (at 400 V AC and nominal values)
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 20 A (-25 °C … 60 °C, UOUT = 24 V DC)
POWER BOOST (IBoost) 26 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 120 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6
Derating 60 °C … 70 °C (2.5 %/K)
Feedback voltage resistance max. 32 V DC
Protection against overvoltage at the output (OVP) < 32 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 3 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 40 mVPP (with nominal values)
Output power 480 W
Peak switching voltages nominal load < 40 mVPP (at nominal values, 20 MHz)
Maximum no-load power dissipation 11 W
Power loss nominal load max. 40 W
Rise time < 0.05 s (UOUT (10 % … 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Fuse protection (secondary side) electronic
thermal-magnetic
thermal
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Switching voltage range 18 V … 24 V
Output voltage + 24 V DC
Maximum inrush current ≤ 20 mA (short-circuit-proof)
Continuous load current ≤ 20 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage 30 V AC/DC
24 V DC
Maximum inrush current 0.5 A
1 A
Continuous load current ≤ 1 A
Signal: POWER BOOST, active
Output description IOUT < IN: High signal
Switching voltage range 18 V … 24 V
Output voltage + 24 V DC
Maximum inrush current ≤ 20 mA (short-circuit-proof)
Continuous load current ≤ 20 mA
Input
Connection method Screw connection
Conductor cross-section, rigid min. 0.2 mm²
Conductor cross-section, rigid max. 6 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section flexible max. 4 mm²
Conductor cross-section AWG min. 18
Conductor cross-section AWG max. 10
Stripping length 7 mm
Screw thread M4
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross-section, rigid min. 0.2 mm²
Conductor cross-section, rigid max. 6 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section flexible max. 4 mm²
Conductor cross-section AWG min. 12
Conductor cross-section AWG max. 10
Stripping length 7 mm
Screw thread M4
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Signal
Conductor cross-section, rigid min. 0.2 mm²
Conductor cross-section, rigid max. 6 mm²
Conductor cross-section flexible min. 0.2 mm²
Conductor cross-section flexible max. 4 mm²
Conductor cross-section AWG min. 18
Conductor cross-section AWG max. 10
Screw thread M4
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Types of signaling LED
Active switching output
Relay contact
Signal output: DC OK active
Status display UOUT > 0.9 x UN: “DC OK” LED green
Note on status display UOUT < 0.9 x UN: Flashing “DC OK” LED
Color green
Note on status display LED flashing
Signal output: DC OK floating
Status display UOUT > 0.9 x UN: “DC OK” LED green
Note on status display UOUT < 0.9 x UN: Flashing “DC OK” LED
Color green
Note on status display LED flashing
Signal output: POWER BOOST, active
Status display IOUT > IN: LED “BOOST” yellow
Color yellow
Number of phases 3
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)
| MESTO | D201925 |
| METASYS | NU-NCM350-8 |
| METRO | MPS-4007 |
| METROSIL | ZB9411015 |
| METSO | D100308 |
| METSO | 02VA0175 |
| METSO | 02VA0193 |
| METSO | 02VA0190 |
| METSO | 02VA0153 |
| METSO | 020A0082 |
| METSO | 02VA0093 |
| METSO | A413125 |
| METSO | A413111 |
| METSO | A413140 |
| METSO | A413150 |
| METSO | A413240A |
| METSO | A413146 |
| METSO | A413152 |
| METSO | A413144 |
| METSO | A413160 |
| METSO | A413110 |
| METSO | A413654 |
| METSO | A413325 |
| METSO | A413665 |
| METSO | D100314 |