HIMA F60DIO24/1601 Safety-Related Controller

Configuring the System ID and the Connection Parameters

To configuring the system ID and the connection parameters

1. Select the resource in the structure tree.

2. Click the Online button located on the Action Bar or select Online on the context menu.

The System Login dialog box is displayed.

3. Click Search.

The Search per MAC dialog box appears.

4. Enter the MAC address valid for the controller – see the label on the housing – and click

Search.

In the dialog box, the values set for IP address, subnet mask and S:R:S are

displayed.

5. If the values for the project are not correct, click Change.

The Write via MAC dialog box appears.

6. Type correct values for the connection parameters and the S.R.S., and enter the access

data for a user account with administrator rigths valid on the controller. Click Write.

Connection data and S.R.S are configured and it is now possible to log in.

For further details, refer to the SILworX manual First Steps (HI 801 103 E).

Loading a Resource Configuration after a Reset

If the compact system is switched on with engaged reset key, it restarts and resets the

connections parameters and user account to the default values (only in case of a

controller). After a new restart with disengaged reset key, the original values are used.

If the connection parameters were modified in the user program, they can be configured in

the compact systems such as described in Chapter 8.2.6.

Logging in as Default User

After configuring the connection parameters and prior to loading the user program, the

default user (administrator with empty password) must be used in the following cases:

The password for the user account is no longer known.

A new user account should be used in the project.

To log in as default user

1. Select the resource in the structure tree.

2. Click the Online button located on the Action Bar or select Online on the context menu.

The System Login dialog box opens.

3. In the IP Address field, select the correct address or use the MAC address.

4. Enter Administrator in the User Group field.

5. Let the Password field empty or cancel the password.

6. Select Administrator in the Access Mode field.

7. Click Log-in.

SILworX isconnected to the HIMatrix controller with default user rights.

Use+A in the System Login dialog box to skip steps 4-6!

8.2.8

8.2.9

Loading a Resource Configuration from the PADT

Before a user program can be loaded with the connection parameters (IP address, subnet

mask and system ID) into the controller, the code must have been generated for the

resource, and ´the connection parameters for PADT and resource must be valid, see

Chapter 8.2.6.

To load a resource configuration from the PADT

1. Select a resource in the structure tree.

2. Click the Online button located on the Action Bar or select Online on the context menu.

3. In the System Login dialog box, enter a user group with administrator rights or write

access.

The Control Panel appears in the workspace and displays the controller state.

4. In the Online menu, select Resource Download.

The Resource Download dialog box appears.

5. Click OK to confirm the download.

SILworX loads the configuration into the controller.

6. Upon completion of the loading procedure, click the Resource Cold Start function on the

Online menu to start the user program.

After the cold start, System State and Program Status enter the RUN state.

The resource configuration is loaded from the PADT.

The Start, Stop and Load functions are also available as symbols on the Symbol Bar.

Loading a Resource Configuration from the Flash Memory of the

Communication System

If data errors were detected in the NVRAM thus causing the watchdog time to be exceeded,

it can be useful to load the resource configuration from the flash memory for the

communication system instead of from the PADT:

If the Control Panel (CP) is no longer accessible, the connection parameters for the project

must be reset in the controller, see Chapter 8.2.6.

If the controller adopts the STOP/VALID CONFIGURATION state after restarting, the user

program can again be started.

If the controller adopts the STOP/INVALID CONFIGURATION state after restarting, the

user program must be reloaded into the NVRAM.

Use the Load Configuration from Flash command to read a backup copy of the last

executable configuration from the flash memory for the communication system transfer it to

HIMA F8620/11
HIMA ELOPII
HIMA F7131   981713102
HIMA F8621A   984862160
HIMA H51q-HS   B5233-1 997105233
HIMA F3322
HIMA F7133
HIMA Z7136
HIMA Z7126
HIMA K9203A   996920360
HIMA F6705
HIMA BV7032-0,5
HIMA EABT3   B9302 997009302
HIMA F8627
HIMA F7533
HIMA F3231

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注