Woodward easYgen-3100/3200 Genset Control for Multiple Unit Operation
easYgen-3100/3200
Genset Control
for Multiple
Unit Operation
The easYgen-3000 Series are control units for genset applications. The numerous inputs and outputs, along
with a modular software structure, permit you to use the easYgen-3000 Series for a wide range of applications.
This includes stand-by, AMF, peak shaving, import-export, cogeneration or distributed generation, among oth
ers. Also the easYgen-3000 Series is compatible for isolated, island parallel, mains parallel and multiple unit
mains parallel operations. The easYgen-3000 Series is able to control up to 32 gensets connected in a network
with automatic sequencing.
The easYgen-3000 Series is available for simple paralleling as well as for complex paralleling applications.
Choose easYgen-3200 should you want to take your fleet of gen-sets parallel to grid or choose easYgen-3500
with LS-5 for multi grid, multi segment applications. These controllers are also available without display, in a
rugged metal housing suitable for back panel installation. A remote panel (RP-3000) can be used for visualiza
tion/control purpose in this case.
FlexAppTM– This feature provides the tools to easily configure the number of operated breakers: None, GCB,
GCB and MCB.
LogicsManagerTM – Woodward’s LogicsManager enables to change the operation sequences and adapt them
to specific needs. The LogicsManager accomplishes this by monitoring a range of measuring values and inter
nal states, which are combined logically with Boolean operators and programmable timers. This enables to
create and/or modify control and relay functions.
FlexInTM– The analog inputs are configurable to operate with VDO, resistive, and/or 0 to 20 mA senders.
Flexible Outputs – Speed and voltage bias outputs are configurable to function with all speed governors and
voltage regulators. The outputs can also be used as freely scalable outputs (e.g. for driving external meters).
FlexCANTM– Advanced network interfaces ensure unsurpassed control performance – from engine control up
to total plant operation. The easYgen-3000 Series is capable of working with common industrial interfaces,
including CAN, RS-232. and RS-485. The multiple communication protocols permit the easYgen-3000 Series to
communicate with a vast majority of engine control units (ECUs), external I/O boards, PLCs, and modems.
CANopen, J1939. Modbus RTU, and Modem protocols are supported.
DynamicsLCDTM– The adaptive and interactive 5.7″, 320×240 pixel color graphical LC display with soft keys
and a clear menu structure ensures intuitive user operation and navigation.
FEATURES
Operation modes: Auto, Stop, Manual, and Load/No Load test modes via discrete input possible
Breaker control: Slip frequency / phase matching synchronization, open-close control, breaker monitoring
Load transfer features: open / closed transition, interchange, soft loading / soft unloading, mains parallel
Remote control via interface and discrete/analog inputs for adjusting speed, frequency, voltage, power, reactive
power, and power factor set points
Freely configurable PID controllers for various control purposes, such as heating circuit control (CHP applica
tions), water level, fuel level, or pressure and/or other process values
Supported ECU: Scania S6. MTU ADEC ECU7/8. Volvo EMS2 & EDC4. Deutz EMR2 & EMR3. MAN
MFR/EDC7. SISU EEM, Cummins and Woodward EGS02 ECU
Discrete and analog I/O expansion board connectivity (Woodward IKD 1 or Phoenix Contact IL series)
Multi-lingual capability: English, German, Spanish, French, Italian, Portuguese, Japanese, Chinese, Russian,
Turkish, Polish, Slovakian, Finnish, Swedish
Configurable voltage/frequency control allows manual control of breakers
Neutral interlocking determines and controls one common neutral in a network of generators
Cylinder temperature monitoring for in-line and V engines
Reactive power regulation at the grid interchange point (kvar or PF)
Power supply …………………………………………………..12/24 VDC (8 to 40 VDC)
Intrinsic consumption ……………………………………………………….. max. 17 W
Ambient temperature (operation) ………………….. -20 to 70 °C / -4 to 158 °F
Ambient temperature (storage) …………………… -30 to 80 °C / -22 to 176 °F
Ambient humidity………………………………………………. 95%, non-condensing
Voltage …………………………………………………………………………………. ( /)
100 Vac [1] Rated (Vrated) …………………………………….. 69/120 VAC
Max. value (Vmax) …………………………………….. 86/150 VAC
Rated surge volt.(Vsurge) ……………………………………………. 2.5 kV
and 400 Vac [4] Rated (Vrated) …………………………………… 277/480 VAC
Max. value (Vmax) …………………………………… 346/600 VAC
Rated surge volt.(Vsurge) ……………………………………………. 4.0 kV
Accuracy ……………………………………………………………………………… Class 1
Measurable alternator windings … 3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w
Setting range ………………… primary …………………………… 50 to 650.000 VAC
Linear measuring range …………………………………………………….. 1.25×Vrated
Measuring frequency……………………………………….. 50/60 Hz (40 to 85 Hz)
High Impedance Input; Resistance per path ……. [1] 0.498 M, [4] 2.0 M
Max. power consumption per path ………………………………………… < 0.15 W
Current (Isolated) Rated (Irated) ………………………… [1] ../1 A or [5] ../5 A
Linear measuring range ……………………………………………….. Igen = 3.0×Irated
Imains/ground = 1.5×Irated
Setting range ……………………………………………………………….. 1 to 32.000 A
Burden ……………………………………………………………………………… < 0.15 VA
Rated short-time current (1 s) ……………………………[1] 50×Irated, [5] 10×Irated
Power ……………………………………………………………………………………………
Setting range …………………………………………………. 0.5 to 99.999.9 kW/kvar
Discrete inputs …………………………………………………………………… isolated
Input range ……………………………………………………..12/24 VDC (8 to 40 VDC)
Input resistance …………………………………………………….. approx. 20 kOhms
Relay outputs ………………………………………………………………………… isolated
Contact material ……………………………………………………………………….. AgCdO
Load (GP) ………………………………………………………………. 2.00 AAC@250 VAC
2.00 ADC@24 VDC / 0.36 ADC@125 VDC / 0.18 ADC@250 VDC
Pilot duty (PD) ……………………………………………………………………………………..
1.00 ADC@24 VDC / 0.22 ADC@125 VDC / 0.10 ADC @250 VDC
Analog inputs (none isolated) ………………………………………..freely scalable
Type ………………………………………………………….. 0 to 500 Ohms / 0 to 20 mA
Resolution …………………………………………………………………………………. 11 Bit
Analog outputs (isolated) ………………………………………………freely scalable
Type ………………………………………………………………. ± 10 V / ± 20 mA / PWM
Insulation voltage (continuously) ……………………………………………….. 100 VAC
Insulation test voltage (1s) ………………………………………………………… 500 VAC
Resolution ………………………………….. 11/12 Bit (depending on analog output)
± 10 V (scalable) ……………………………………… internal resistance ≤1 kOhms
± 20 mA (scalable) ………………………………………… maximum load 500 Ohms
Housing Front panel flush mounting ……………… Plastic housing
Dimensions WxHxD …………………………………… 282 × 217 × 99 mm
Front cutout WxH ……………………………. 249 [+1.1] × 183 [+1.0] mm
Connection ………………………………………………. screw/plug terminals 2.5 mm²
Front ………………………………………………………………………… insulating surface
Sealing Front ……………………………. IP66 (with screw fastening)
Front ……………………………. IP54 (with clamp fastening)
Back ……………………………………………………………. IP20
Weight …………………