Woodward MFR300-71M 8444-1091 8444-1092
Woodward MFR300-71M 8444-1091 8444-1091
Accuracy …………………………………………………………………………… Class 0.5
Power supply …………………………………………………. 12/24 Vdc (8 to 32 Vdc)
Intrinsic consumption ………………………………………………………….. max. 5 W
Ambient temperature (operation) ……………. -20 °C (-4 °F) / 70 °C (158 °F)
Ambient temperature (storage) …………….. -40 °C (-40 °F) / 85 °C (185 °F)
Ambient humidity ……………………………………………… 95 %, non-condensing
Voltage ……….. Rated value /∆: [1] 69/120 Vac or [7] 400/690 Vac
Rated voltage Vph-ground: [1] 150 Vac or [7] 600 Vac
Max. cont. voltage Vph-ph: [1] 150 Vac or [7] 862 Vac
Rated surge voltage: [1] 2.5 kV or [7] 6.0 kV

Measuring frequency ……………………………………………………….. 45 to 65 Hz
Linear measuring range …………………………………………………… 1.25 × Vrated
Input resistance ……………………………………………………………… [1] >0.5 MΩ
[7] >2.0 MΩ
Max. power consumption per path …………………………………………… 0.15 W
Current (Irated) ……………………………………………………….. [1] ../1 A, [5] ../5 A
Linear measuring range ………………………………………………………… 3 × Irated
Max. power consumption per path ……………………………………….. < 0.15 VA
Rated short-time current (1 s) …………………………….. [1] 10 Aac, [5] 50 Aac
Relay outputs …………………………………………………………………….. isolated
Contact type ……………………………………………………..Form C (change-over)
Contact material ……………………………………………………………………. AgCdO
Load (GP) ……………………………………………………………. 2.00 Aac@250 Vac
………………..2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Pilot duty (PD) ………………………………………………………………………………….
………………..1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Housing ………………………………………………. Type Extrusion profile UM122
for DIN rail mounting
Dimensions …………………………………………………………. 146 × 128 × 50 mm
Connection ………………………………………… screw/plug terminals depending
on connector 2.5 mm² (14 AWG)
Protection system ……………………………………………………………………… IP20
Weight ………………………………………………………………………… approx. 300 g
Disturbance test (CE) ………. tested according to applicable EN guidelines
Listings …………………………… UL/cUL listed (File No.: E231544), GOST-R
PART NUMBERS
Model Rated PT secondary Rated CT secondary Mounting Part Number (P/N)
MFR300-11M 100 Vac [1] ../1 A [1] DIN rail [M] 8444-1089
MFR300-15M 100 Vac [1] ../5 A [5] DIN rail [M] 8444-1090
MFR300-71M 690 Vac [7] ../1 A [1] DIN rail [M] 8444-1091
MFR300-75M 690 Vac [7] ../5 A [5] DIN rail [M] 8444-1092
MFR300-75M/SU03 690 Vac [7] ../5 A [5] DIN rail [M] 8444-1093
MFR300-75M/K28 690 Vac [7] ../5 A [5] DIN rail [M] 8444-1094
In this general application the device is used as a
transducer with monitoring functions. The control does not
operate any breaker.
• PLC measuring data V, f, I, Pact, Preact
• Monitoring V, f, I, Pact, Preact
In this generator related application the device is used as a
transducer with monitoring functions. The control can be
used to open a breaker.
• Generator measuring data V, f, I, Pact, Preact
• Monitoring V, f, I, Pact, Preact
In this mains related application the device is used as a
transducer with monitoring functions. The control can be
used to open a breaker.
• Mains measuring data V, f, I, Pact, Preact
• Monitoring V, f, I, Pact, Preact
| HIMA | X-DI1601 985210222 |
| HIMA | X-BLK01 632590802 |
| HIMA | X-DO1201 985210204 |
| HIMA | F7131 |
| HIMA | F7553 984755302 |
| HIMA | F3330 984333002 |
| HIMA | F3237 984323702 |
| HIMA | F6217 984621702 |
| HIMA | H51q-H B5233-2 997235233 |
| HIMA | Z7149 |
| HIMA | H4135 992413502 |
| HIMA | K9202 996920202 |
| HIMA | F8652X 984865265 |
| HIMA | H41q-HS B4237-1 997104237 |
| HIMA | F7130A 984713060 |
| HIMA | F8627 984862702 |