Woodward: easYgen-3400XT (P1) 8440-2084
Product number: 8440-2087
Manufacturer product number: 8440-2087
Description: Woodward: easYgen-3400XT (P2), Genset Controller 1A/5A
The discrete inputs may be grouped into two categories:
n Programmable–The discrete input has been assigned a default function
using either the LogicsManager or preconfigured alarms
such as “emergency stop”.– The following sections describe how these functions are
assigned.– The function of a discrete input can be changed if required.– The following description of the inputs, labeled with “pro
grammable”, refers to the preconfiguration.
n Fixed– The discrete input has a specific function that cannot be
changed depending upon the configured application mode.
Input Type/Preset Description
Discrete input [DI 01] Programmable
Preconfigured to “Emergency stop”
This discrete input is configured as alarm class F and is not
delayed by the engine speed.
Discrete input [DI 02] Programmable
Preconfigured to “Start in AUTO”
Enabled in the AUTOMATIC operation mode
This discrete input is configured as a Control input in the alarm
class and is not delayed by the engine speed.
n Energized
If the unit is in the AUTOMATIC operation
mode (selected with the operating mode selec
tion push button on the front panel) the con
trolled engine is started automatically.
n De-energized
The engine is stopped.
Discrete input [DI 03] Programmable
Preconfigured to “Low oil pressure”
This discrete input is configured as alarm class B and is
delayed by the engine speed.
Discrete input [DI 04] Programmable
Preconfigured to “Coolant temperature”
This discrete input is configured as alarm class B and is not
delayed by the engine speed.
Discrete input [DI 05] Programmable
Preconfigured to “Alarm acknowledge”
This discrete input is used as a remote acknowledgement for
alarms. The input is normally de-energized. When an alarm is
to be acknowledged the input is energized. The first time an
alarm in acknowledged, the centralized alarm/horn is silenced.
When the input is energized a second time, all alarms, which
are no longer active, will be acknowledged.
This discrete input is configured as a Control input in the alarm
class and is not delayed by the engine speed.
Discrete input [DI 06] Programmable
Preconfigured to “Enable MCB”
Only applicable for application mode
This discrete input is configured as a Control input in the alarm
class and is not delayed by the engine speed.
n Energized

8440-2084
The MCB is enabled and closure of the
breaker is permitted.
n De-energized
The MCB is not enabled and closure of the
breaker is not permitted. This function permits
a supervisory control (i.e. a PLC) to allow the
closure of the MCB by the easYgen.
Discrete input [DI 07] Fixed to “Reply: MCB open” Only applicable for application mode
This input implements negative function logic.
The controller utilizes the CB auxiliary (B) contacts into this dis
crete input to reflect the state of the MCB.
This discrete input must be energized to show when the
breaker is open and de-energized to show when the MCB is
closed. The status of the MCB is displayed on the screen.
This input is usually used in all breaker modes to change
between frequency/voltage and power/power factor control
(refer to note below).
Discrete input [DI 08] Fixed to “Reply: GCB open” Only applicable for application modes and
This input implements negative function logic.
The controller utilizes the CB auxiliary (B) contacts into this dis
crete input to reflect the state of the GCB. This discrete input
must be energized to show when the breaker is open and de
energized to show when the GCB is closed. The status of the
GCB is displayed on the screen.
This input is usually used in all breaker modes to enable
reverse power protection, overload MOP protection, mains
decoupling and the activation of the load sharing (refer to note
below).
Discrete input [DI 09] Programmable
Preconfigured for “Alarm class B”
This discrete input is not delayed by the engine speed.
Discrete input [DI 10] Programmable
Preconfigured for “Alarm class B”
This discrete input is not delayed by the engine speed
n Programmable– The discrete output has been assigned a default function
using the LogicsManager.– The following text describes how these functions are
assigned using the LogicsManager.– It is possible to change the function of the discrete output if
required.– The following description of the outputs, labeled with “pro
grammable”, refers to the preconfiguration.
n Fixed– The discrete output has a specific function that cannot be
changed depending upon the configured application mode.– The discrete output cannot be viewed or changed in the
LogicsManager.– However, the discrete output may be programmable in
some application modes.
| ABB | THYRISTOR MODUL WE-73-10/CH 64421956 |
| ABB | 969.105EBG 540KKS166899 |
| ABB | 3BHE024577R0101 PPC907BE AMC34 |
| ABB | CH-3185 3BHL000986P1006 |
| ABB | 500MBA01 1MRB150003R0002 1MRB200053/L |
| ABB | 500MBA02 1MRB150003R000/B |
| ABB | 500MBA02 1MRB150003R0003 1MRB200053/M |
| ABB | 3BHE022294R0103 GFD233A103 |
| ABB | 3BHE023784R1023 PP D113 B01-10-150000 |
| ABB | 4LA41100102V1.2 KB2 |
| ABB | 3BSE076940R1 PM862K01 AC 800M |
| ABB | 560PSU02 1KGT011900R0001 |
| ABB | PPD113 B03-23-100110 3BHE023584R2334 |
| ABB | XFD213A 3BHE028122R0001 |
| ABB | PFVO102 PFVO142 3BSE023732R1 |
| ABB | PM891 3BSE053240R1 |
| ABB | PPD513A0E110110 3BHE039724R0E41 |
| ABB | REF630 1KHL160003R0001CR |