Woodward: easYgen-3400XT (P1) 8440-2084
Parameter CL Setting range
[Default]
Description
1785 Mains rated
current
2 5 to 32000 A
[300 A]
This value specifies the mains rated current, which is used as a reference
figure for related functions.
1858 1Ph2W voltage
measuring
3 [Phase
phase]
The unit is configured for measuring phase-phase voltages if 1Ph 2W meas
uring is selected.
Phase – neutral The unit is configured for measuring phase-neutral voltages if 1Ph 2W meas
uring is selected.
Notes
| ABB | KTO 011 KTO011 |
| ABB | KTS 011 KTS011 |
| ABB | TNR 25590 TNR25590 |
| ABB | 3BHE006373R0101 XVC769 AE101 HIEE410506P104 |
| ABB | SCYC51204 63912476 |
| ABB | SCYC51204 63912476C |
| ABB | SCYC51213 63911607C |
| ABB | FPX86-9364-A |
| ABB | SCYC51220 |
| ABB | HL000986P0006 |
| ABB | HIES208441R |
| ABB | 3BHB005243R0105 KUC755AE105 |
| ABB | 3BHB004791R0101 |
| ABB | 3BHB009175R0001 |
| ABB | 3BHE034863R0001 UDC920BE01 |
| ABB | MTA025 EBG92026 |
| ABB | HIES308461R |
For information on measuring principles refer to Ä Chapter 3.2.5.1 “Generator
Voltage” on page 47.
Never configure the busbar measurement for phase-neutral, if the other sys
tems like mains and generator are configured as 3Ph 3W or 3Ph 4W. The
phase angle for synchronization would be not correct.
1859 1Ph2W phase
rotation
3 [CW] A clockwise rotation field is considered for 1Ph 2W measuring .
CCW A counter-clockwise rotation field is considered for 1Ph 2W measuring.
Notes
For information on measuring principles refer to Ä Chapter 3.2.5.1 “Generator
Voltage” on page 47.
1851 Generator
voltage meas
uring
2 3Ph 4W OD Measurement is performed Line-Neutral (Open Delta connected system). The
voltage is connected via transformer with 3 Wire.
Phase voltages and the neutral must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
Open Delta connected systems.
Monitoring refers to the following voltages:
n VL12. VL23 and VL31
1Ph 3W Measurement is performed Line-Neutral (WYE connected system) and Line
Line (Delta connected system). The protection depends on the setting of
parameter 1770 Ä p. 109.
Measurement, display, and protection are adjusted according to the rules for
single-phase systems.
Monitoring refers to the following voltages:
n VL13 (parameter 1770 Ä p. 109 configured to “Phase
phase”)
n VL1N, VL3N (parameter 1770 Ä p. 109 configured to
“Phase-neutral”)
1Ph 2W Measurement is performed Line-Neutral (WYE connected system) if param
eter 1858 Ä p. 99 is configured to “Phase – neutral” and Line-Line (Delta con
nected system) if parameter 1858 Ä p. 99 is configured to “Phase – phase”.
Measurement, display and protection are adjusted according to the rules for
phase-phase systems.
Monitoring refers to the following voltages:
n VL1N, VL12
3Ph 3W Measurement is performed Line-Line (Delta connected system). Phase vol
tages must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
Delta connected systems.
Monitoring refers to the following voltages:
n VL12. VL23. VL31
ID Parameter CL Setting range
[Default]
Description
[3Ph 4W] Measurement is performed Line-Neutral (WYE connected system) and Line
Line (Delta connected system). The protection depends on the setting of
parameter 1770 Ä p. 109.
Phase voltages and the neutral must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
WYE connected systems.
Monitoring refers to the following voltages:
n VL12. VL23 and VL31 (parameter 1770 Ä p. 109 config
ured to “Phase-phase”)
n VL1N, VL2N and VL3N (parameter 1770 Ä p. 109 config
ured to “Phase-neutral”)
Notes

8440-2084
If this parameter is configured to 1Ph 3W, the generator and mains rated vol
tages (parameters 1766 Ä p. 98 and 1768 Ä p. 98) must be entered as Line
Line (Delta) and the busbar 1 rated voltage (parameter 1781 Ä p. 98) must
be entered as Line-Neutral (WYE).
For information on measuring principles refer to Ä Chapter 3.2.5.1 “Generator
Voltage” on page 47.
1850 Generator cur
rent measuring
2 [L1 L2 L3 ] All three phases are monitored. Measurement, display and protection are
adjusted according to the rules for 3-phase measurement. Monitoring refers
to the following currents: IL1. IL2. IL3
Phase L{1/2/3} Only one phase is monitored. Measurement, display and protection are
adjusted according to the rules for single-phase measurement.
Monitoring refers to the selected phase.
Notes
This parameter is only effective if generator voltage measuring (param
eter 1851 Ä p. 99) is configured to “3Ph 4W” or “3Ph 3W”.
For information on measuring principles refer to Ä Chapter 3.2.6.1 “Generator
Current” on page 66.
1853 Mains voltage
measuring
2 [3Ph 4W] Measurement is performed Line-Neutral (WYE connected system) and Line
Line (Delta connected system). The protection depends on the setting of
parameter 1771 Ä p. 135.
Phase voltages and the neutral must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
WYE connected systems.
Monitoring refers to the following voltages:
n VL12. VL23 and VL31 (parameter 1771 Ä p. 135 config
ured to “Phase-phase”)
n VL1N, VL2N and VL3N (parameter 1771 Ä p. 135 config
ured to “Phase-neutral”)
n VL12. VL23. VL31. VL1N, VL2N and VL3N (parameter
1771 Ä p. 135 configured to “All”)
3Ph 3W Measurement is performed Line-Line (Delta connected system). Phase vol
tages must be connected for proper calculation.
Measurement,