UniOP ePAD04 ePAD04-D046 Universal Operator Panel
ePAD04
Universal Operator Panel
ePAD04 Display Features
LCD Graphic Display
120×32 pixels.
ASIC/2 driver supports
ASIC/2 and SINC/3 product
families
ASIC/1 driver supports
ASIC/1 product families.
Data display in numerical,
text and bargraph format
RS-232 or RS-485
Communication with gapping
No programming needed.
Intuitive Designer software.
Alarms and historical alarm
list
Eight passwords for
protection
The ASI/Exor Universal Operator Panel, ePAD04. is a cost effective Human
Machine Interface for the ASI Controllers. It allows the display controller
status, the modification of setpoints and schedules, intervention in controller
operation via overrides, and to annunciate and acknowledge alarms.
A bright LCD display with backlight provides clear visual indication. A
membrane keypad provides and attractive yet resilient means of data entry in a
variety of environments.
The ASIC/2 driver supports ASIC/2 and SINC/3 controller products The
ePAD04 interacts with the ASIC/2-7040 or ASIC/2-8040 on the system or
local bus at 9600 baud. Gapping allows coexistence with communication with
other controllers and/or the building management software. The ASIC/1
driver supports ASIC/1 controller products.
The ePAD04 is configured using powerful and intuitive Designer software
with the ASIC/2 driver. Data from one or more controllers can be placed on a
series of screens. The choice of data to be displayed is made at the time the
ePAD04 is configured. The configuration is kept in non-volatile memory so
that it does not lose program data during power interruption.
The ePAD04 is page based. The operator can select one of its pages. Data is
accessed by scrolling up or down the page. The page structure allows rapid
access to data. Numeric data can be scaled, or used to display one of a list of
messages. Binary data can display different on and off labels. Controller labels
such as Description, and Input, Output, and Schedule Names can be displayed
as strings.
Display items can be read/write. Pressing a function key places the panel in
download mode. You can move to and select the downloadable item you wish
to change, and then
use the arrow keys to
change the value.
Pressing return sends
the
value to the
controller. Up to 8
passwords can be
configured to allow
access or download to
a range of pages, so
that users can see or
change only needed
information.
Specifications
Display
Graphic Display: LCD, Monochrome
Backlight LCD
Graphic resolution 120×32 pixels
Active area 70×21 mm
Rows/columns 4×20
Scalable fonts Yes
User definable characters 256
Contrast regulation Software
Memory
User memory 512 KB
Function keys 4. with slide-in legend
System keys 7. Up,Down, Left, Right,
Return, Cancel,User
LED’s 4 Function, 1 User,
4 System
Connections
PLC port RS-232. RS-485
Programming speed 9600 bps
Power
Supply voltage 18 – 30 Vdc
Max power consumption 250 mA @24 Vdc
Fuse Overcurrent protection device
Features
Dual-driver capability Yes
Alarms 1024
Alarm info page Yes
Password Yes, 8 levels
Physical
Weight
Operating temperature 0 to +50 °C
Storage temperature -20 to +70 °C
Operating and storage humidity 5 to 85 % RH
non-condensing
Compliance
CE Emitted interference EN 50081-2. 1993
CE Noise immunity EN 61000-6-2. 2000
UL Recognized Component File E183499
NWGQ2. Information Technology Equipment
Front Dimensions and Cutout
Faceplate LxH 149×109 mm (5.86″x4.29″)
Cutout AxB 136×96 mm (5.35″x3.78″)
Cutout depth C 53 mm (2.08″)
Max panel thickness 5 mm (0.19″)
Cables
RS-232 Communication DB-15S(F) to DB-9P(M)
RS-485 Communication DB-15S(F) to Block
RS-232 Programming DB-15S(F) to DB-9S(F)
How to Order: Order Number
ASI Exor Universal Operator Panel ePAD04
Accessories: Order Number
Power Supply 24 Vac to 24 Vdc ASI/PS1.5
ePAD Communicaton Cable ePAD Comm Cable
ePAD Programming Cable ePAD Prog Cable
Software is supplied by download from website,
or on CD-ROM by request.
LEDs Color Status Meaning
OFF No hardware problem detected red
ON Hardware fault
OFF No key pressed
FAULT
KEY green
ON Key pressed (visual feedback)
OFF Hardware fault
HDW
green
ON Unit in operation
BLINK Communication error
COM
green
ON Communication OK
OFF No alarms
BLINK Alarm requires acknowledgment
Alarms
red
ON Alarm active
USER green User controlled LED