Stucke Elektronik SYMAP®G generator protection
SYMAP® G is a high-end digital protection relay from the German manufacturer Stucke Elektronik.
1 Unlike the integrated ECG model, the SYMAP® G is specifically dedicated to Generator Protection,
providing a comprehensive suite of electrical monitoring and safety functions to ensure the integrity of the alternator in power generation systems.
1. Product Description
SYMAP® G is a microprocessor-based protection device designed for low, medium, and high-voltage generators.
2 Its primary role is to detect electrical faults within the generator or between the generator and the busbar.
It offers high-precision measurement and rapid tripping capabilities to prevent catastrophic mechanical or electrical failure.
It is often used in systems where engine control is handled by a separate PLC or specialized controller, focusing purely on high-grade electrical protection.
2. Technical Parameter Table
Category Specification
Power Supply 24V DC (Standard) or 110V/230V AC/DC (Optional)
Current Inputs 3-phase ($I_1. I_2. I_3$) + 1 Neutral ($I_o$) / 1A or 5A rated
Voltage Inputs 3-phase ($U_1. U_2. U_3$) + 1 Synch-Voltage / Up to 690V direct
Frequency Range 40 Hz – 70 Hz (Accuracy: 0.01 Hz)
Protection Functions Overcurrent (50/51), Reverse Power (32), Over/Under Voltage (59/27), Over/Under Frequency (81U/O), Negative Sequence (46), Differential Protection (87G – optional)
Measurement Accuracy Voltage/Current: 0.5%; Power/Energy: 1.0%
Communication Modbus RTU/TCP, Profibus DP, CANopen, IEC 61850
Operating Temp -20°C to +70°C
HMI Display Backlit Graphic LCD with multi-language support
3. Related Models
The SYMAP® G series varies based on the complexity of the protection required:
SYMAP® G: Standard generator protection for basic and medium applications.
SYMAP® G-Diff: Enhanced version featuring Generator Differential Protection (ANSI 87G), used for large-scale generators to detect internal winding faults.
SYMAP® G-HV: High Voltage version designed to interface with Voltage Transformers (PTs) and Current Transformers (CTs) in MV/HV grids.

SYMAP®G
4. Application Cases
Commercial Shipping: Protection for main alternators on cargo ships, tankers, and cruise liners.
Power Plants: Used in thermal, hydro, or diesel power stations as the primary electrical safety guard for the generator.
Offshore Platforms: Reliable protection for generators operating in harsh environments with high vibration and salt mist.
Critical Infrastructure: Backup power systems for hospitals and data centers where generator stability is vital.
5. Product Advantages and Features
High Reliability: Features a multi-processor architecture (3-CPU system) to ensure that protection functions remain active even if the HMI or communication processor fails.
Comprehensive ANSI Library: Includes all standard protection codes required by international grid codes and maritime authorities.
Disturbance Recording: Captures high-resolution waveforms during fault events, allowing engineers to analyze the “root cause” of a trip.
Flexible Logic (PLC): Integrated “Boolean” logic editor allows users to create custom interlocking and alarm sequences without external hardware.3
Rugged Construction: Metal housing with excellent EMC shielding, certified by major classification societies (DNV, LR, ABS, etc.).
6. Other Models in the Same Series
Stucke Elektronik provides a modular ecosystem for the entire power plant:
SYMAP® EC: Engine Control only (governor and start/stop logic).
SYMAP® ECG: The “All-in-One” solution (Engine Control + Generator Protection).
SYMAP® F: Feeder Protection for outgoing distribution lines.
SYMAP® BC: Bus-tie Control for managing busbar couplers.
SYMAP® T: Transformer Protection for step-up or step-down units.