Woodward 03365 505E (Extraction / Admission)
Product Specification 03365
505E (Extraction / Admission)
Digital Control for Steam Turbines Applications
The 505E controller is
designed to operate
single-extraction
and/or admission
steam turbines of all
sizes and
applications. This
steam turbine
controller includes
specifically designed
algorithms and logic
to start, stop, control,
and protect single
extraction and/or
admission steam
turbines or turboexpanders, driving generators, compressors, pumps, or industrial fans. The 505E
control’s unique PID structure makes it ideal for applications where it is required to
control steam plant parameters like turbine speed, turbine load, turbine inlet
pressure, exhaust header pressure, extraction or admission header pressure, or tie
line power.
The control’s special PID-to-PID logic allows stable control during normal turbine
operation and bumpless control mode transfers during plant upsets, minimizing
process over- or undershoot conditions. The 505E controller senses turbine speed
via passive or active speed probes and controls the steam turbine through HP and
LP actuators connected to the turbine steam valves.

03365
The 505E controller senses extraction and or admission pressure via a 4–20 mA
transducer and uses a PID through a ratio/limiter function to accurately control
extraction and/or admission header pressure, while protecting the turbine from
operating outside of its designed operating envelope. The controller uses the specific
turbine’s OEM steam map to calculate its valve-to-valve decoupling algorithms and
the turbine operating and protection limits.
Description
The 505E control is packaged in an industrial hardened enclosure designed to be
mounted within a system control panel located in a plant control room or next to the
turbine. The control’s front panel serves as both a programming station and operator
control panel (OCP). This user-friendly front panel allows engineers to access and
program the unit to the specific plant’s requirements, and plant operators to easily
start/stop the turbine and enable/disable any control mode. Password security is
used to protect all unit program mode settings. The unit’s two-line display allows
operators to view actual and setpoint values from the same screen, simplifying
turbine operation.
Turbine interface input and output wiring access is located on the controller’s lower
back panel. Unpluggable terminal blocks allow for easy system installation,
troubleshooting, and replacement.
Cost‐Effective Design
The 505E control is designed to function as the turbine control,
system sequencer, operator control panel, and first-out
indicator. This encompassing design minimizes external
system devices as well as system installation, wiring, and
troubleshooting.
This field configurable controller allows major functional changes
to be made at site, often by knowledgeable plant personnel, and
minor functional changes to be on-line as process changes
require. The 505E control’s first-out-indicator logic indicates
internal as well as external system related alarm and shutdown
conditions, greatly simplifying and reducing system
troubleshooting.
Communications
The 505E controls can communicate directly with plant
Distributed Control Systems and/or CRT-based operator
control panels, through two Modbus® * communication ports.
These ports support RS-232. RS-422. and RS-485
communications using ASCII or RTU Modbus protocols.
Communications between the 505E and a plant DCS can also
be performed through hardwired connections. Since all 505E
PID setpoints can be controlled through analog input signals,
interface resolution and control is not sacrificed.
*—Modbus is a trademark of Schneider Automation Inc.
System Protection
Integral Overspeed Protection Logic
First-out Indication (10 individual shutdown inputs)
Turbine Operating Envelope Limiters
Bumpless transfer between control modes if a transducer
failure is detected
Local/Remote Control priority and selection
Failsafe Shutdown Logic
Control
The following PIDs are available to perform as process
controllers or limiters:
Speed/Load PID (with Dual Dynamics)
Extraction / Admission PID
Auxiliary PID (limiter or control)
Cascade PID (Header Pressure or Tie-Line Control)
Control Specifications
INPUTS

Power: 18–32 Vdc, 90–150 Vdc, 88–132 Vac
(47–63 Hz), 180–264 Vac (47–63 Hz)
Speed: 2 MPUs (1–30 Vrms) or proximity probes
(24 Vdc provided), 0.5 to 15 kHz
Discrete Inputs: 16 Contact Inputs (4 dedicated,
12 programmable)
Analog Inputs: 6 Programmable Current Inputs
(4–20 mA)
OUTPUTS
Valve/Actuator Drivers: 2 Actuator Outputs (4–20 mA or
20–160 mA)
Discrete Outputs: 8 Relay Outputs (2 dedicated,
6 programmable)
Analog Outputs: 6 Programmable Current Outputs
(4–20 mA)
COMMUNICATION
Serial: 2 Modbus (ASCII or RTU) Comm Ports
(RS-232. RS-422. or RS-485 compatible)
Control Accessories
Control Assistant (Configuration Management Tool)
The Woodward Control Assistant software program is a
computer-based service tool that can be used with the 505E
control to upload, save, and download controller
configurations. Optionally, this service tool can also be used to
trend unit parameters, to compare differences in configuration
files, and to verify if control settings have been changed.
Functionality
The 505E’s control capabilities are:
Speed/Frequency Control
Extraction / Admission Header Pressure Control
Turbine or Generator Load Control or Limiting
Turbine Inlet Header Pressure Control or Limiting
Turbine Exhaust Header Pressure Control or Limiting
Plant Import/Export Power Control or Limiting
Isochronous Load Sharing between units (with DSLC™
control)
Features
Critical Speed Avoidance (3 speed bands)
Auto Start Sequence (hot & cold starts)
Valve Limiter(s)
Security (Program is Password Protected)
Dual Speed/Load Dynamics
First-Out Indication (Shutdowns)
Zero Speed Detection with proximity probe (< 0.5 Hz)
Peak Speed Indication for overspeed trip
Two Programmable Functions Keys on the 505E’s front
panel
Two independent Modbus comm links
Remote analog setpoints for Speed/Load, Ext/Adm, Aux,
and Cascade
Program upload/download capability
Feed-forward decoupling algorithm for compressors
Operating Conditions
–25 to +65 °C ambient air temperature range
Optional NEMA type 4 (watertight and dust-tight, indoor/outdoor) enclosure for bulkhead mounting with a temperature range
from –25 to +55 °C
Approximate dimensions 14L x 11H x 4D inches (356 x 279 x 102 mm)
Approximate bulkhead enclosure dimensions 20L x 20H x 7.6D inches (508 x 508 x 193 mm)
Humidity: Lloyd’s ENV2 test #1
Dry heat: Lloyd’s ENV3
Salt fog: US MIL-STD-810 method 509.2 procedure 1
Shock: meets US MIL-STD-810C, method 516.2-1. procedure 1B
Vibration: Lloyd’s ENV2 test #1
Certifications: CE (18–32 Vdc version only), UL, & cUL
Pollution Resistance
Particulate Pollution Resistance: IEC 664-1 Pollution Degree 2 (Normally only nonconductive pollution occurs. Temporary
conductivity caused by condensation is to be expected.)
Gaseous Pollution Resistance: The polyacrylate conformal coating withstands NO2. CO2. SO2. and H2S gases per IEC
60068-2-60:1995 Part 2.60 Methods 1 and 4 (Flowing Mixed Gas Corrosion Test). It will withstand levels typical of
telecommunications and computer installations as defined by Battelle Labs Class III (between IEC 60721-3-3 classification
3C1 and 3C2. light industrial to urban industrial, heavy traffic).