LAMBDA LZS-1500-3 Single Output Industrial Power Supplies
LZS/SE Series
Single Output Industrial Power Supplies
Features
u -40ºC to +71ºC operation
u MIL-STD-810E Vibration / Shock
u Input transient protected
u Wide range output adjustment
u Single wire current share
u Conducted EMI Class B
u 5 Year Warranty
u Rugged mechanical design
u Superior thermal design
Key Market Segments & Applications
u Factory Automation
5V Output Models 12V Output Models 24V Output Models
(-1) (-2) (-3)
AAC Input Voltage – LZS: 85-132 / 170-265VAC Auto select, SE: 105-140VAC (170VAC for 1min.)
AC Input Frequency – LZS: 47 – 440Hz, SE: 47 – 63Hz
DC Input Voltage Range – LZS: 220 – 380VDC
Inrush Current (110 / 220VAC) A 250W & 500W: 20 / 40A. 750W, 1000W & 1500W: 40 / 80A
Effi ciency (typical) % 75%, (72% on 250W models)
Ripple & Noise – 10mV RMS, 35mV Pk-Pk 10mV RMS, 50mV Pk-Pk 10mV RMS, 100mV Pk-Pk
Line Regulation % 0.1% from low AC line to high AC line
Load Regulation % 0.1% from no load to full load

LZS-1500-3
Transient Response – Recovers to within 50ms, max deviation 7.5% -1 models, 5% -2 & -3 models
Overcurrent Protection – ~ 110% of rated current, auto recovery
Overvoltage Protection V User adjustable from front panel
Thermal Protection – Internal thermostat. Recycle AC to reset
Hold Up Time (Typical) ms 26ms (at 115VAC)
Remote Sense – Compenstates for a total of 1.0V cable drop
Remote Adjust – Using front panel potentiometer, Resistance (1k/V), or Voltage (1V/V)
Remote On / Off – TTL compatible, active high
Signals – Optocoupled transistor for AC Fail, DC Good, Inverter OK
Indicators – Green LED indicates output good, red LED indicates overvoltage or over temperature
Parallel Connection – Single wire current share
Operating Temperature ºC -40~+71ºC, derate as shown in model selector, 20 minute warm up period needed for <-30ºC
Storage Temperature ºC -55 to +85ºC
Temperature Coeffi cient – 0.025%/ºC
Humidity (non condensing) %RH 5 – 95%RH
Cooling – Internal fan
Withstand Voltage – Input – Ground 1.5kVAC, Input – Output 3kVAC, Output – Ground 500VAC
Vibration – MIL-STD-810E, Method 516.4 Proc. I, II, IV, VI
Shock – MIL-STD-810E, Method 514.4. Category 1. 9
Safety Agency Approvals – UL60950. CSA60950. EN60950. & CE Mark (LVD)
Conducted & Radiated EMI – VDE0871 Curve B, FCC Part 15. subpart J, Class B, MIL-STD-461D, CE102
Weight (Net / Shipping) lbs 250: 7/9; 500: 10/12; 750: 11/14; 1000: 15.5/19.5; 1500: 22/26
Size (WxHxD) – See outline drawings
LZS250-1 5 4.5 – 6.3 50 45 40 30
LZS500-1 5 4.5 – 6.3 100 90 80 60
LZS750-1 5 4.5 – 6.3 150 135 120 90
LZS1000-1 5 4.5 – 6.3 200 190 160 120
LZS1500-1 5 4.5 – 6.3 300 270 240 180
LZS250-2 12 10 – 15.75 21 18.9 16.8 12.6
LZS500-2 12 10 – 15.75 42 37.5 33.5 27
LZS750-2 12 10 – 15.75 63 56.5 50 37.5
LZS1000-2 12 10 – 15.75 83 80 67 50
LZS1500-2 12 10 – 15.75 125 112.5 100 75
LZS250-3 24 18 – 29.4 12.5 11.3 10 7.5
SE250-3 24 18 – 29.4 12.5 11.3 10 7.5
LZS500-3 24 18 – 29.4 25 22.5 20 16.5
SE500-3 24 18 – 29.4 25 22.5 20 16.5
LZS750-3 24 18 – 29.4 37.5 33.5 30 22.5
SE750-3 24 18 – 29.4 37.5 33.5 30 22.5
LZS1000-3 24 18 – 29.4 50 48 40 30
SE1000-3 24 18 – 29.4 50 48 40 30
LZS1500-3 24 18 – 29.4 75 67.5 60 45
SE1500-3 24 18 – 29.4 75 67.5 60 45
O