Secure analog I/O package IS220YAICS1AL
GE IS220YAICS1AL is a safety analog I/O package (YAIC) of the Mark VIeS series, focusing on analog signal acquisition and conditioning at SIL2/3 safety level.
It is compatible with the safety circuits of critical industrial controls such as gas turbines and supports combination with multiple safety terminal boards.
Achieve high-precision analog quantity access and secure isolation. The following are the core information and technical details:
I. Core Positioning and Basic Attributes
Project parameters
Model IS220YAICS1AL (often written as IS220YAICS1A, where L is the suffix for batch/version)
Brand GE Vernova
Series Mark VIeS (Security Enhanced Type)
Type Safety Analog I/O Pack (Safety Analog I/O Pack)
Safety level SIL2/3 compatible
Redundancy supports simplex/TMR (Triple Module Redundancy)
The matching terminal boards include IS200STAIS1A/2A, IS400STAIS1A/2A, IS200/400TBAIS1C, etc
Communication IONet Ethernet, real-time interconnection with UCSC/UCSB controllers
Ii. Key Technical Specifications
Channel capability:
16 channels of high-precision analog input, supporting industrial standard signals such as 4-20mA, 0-20mA, 0-10V, and ±10V.
Accuracy and resolution:
16-bit AD conversion, accuracy ±0.05%, reading ±0.01%, range, 1500V AC isolation between channels, strong anti-interference ability.

IS220YAICS1AL
Power supply and environment:
24V DC power supply, power consumption approximately 6W; Operating temperature: 0-60℃, humidity: 5%-95%, no condensation.
Safety features:
Channel-level fault diagnosis, open circuit/short circuit detection, support for fault-safe output and voting logic of safety circuits.
Iii. Core Functions and Applications
Safety simulation acquisition:
Adjust the analog signals from on-site sensors (such as pressure, temperature, and displacement), convert them into digital quantities that the controller can read, and adapt to safety-critical circuits.
Isolation and protection:
Achieve electrical isolation between the on-site side and the logic side to prevent surge/overvoltage damage to the control system and ensure the stability of the safety circuit.
Fault diagnosis:
Real-time monitoring of channel status, diagnosis of faults such as open circuit, short circuit, and drift, triggering safety responses, and enhancing system availability.
Typical applications:
safety-related analog quantity access scenarios such as safety shutdown circuits for gas turbines, safety monitoring of fuel flow/pressure, and overspeed protection for steam turbines.
Iv. Selection and Supporting Tips
Terminal board matching:
Select the corresponding safety terminal board based on the signal type (such as thermocouple, 4-20mA). For TMR configuration, 3 sets of I/O packages + 3 sets of terminal boards are required.
Signal adaptation:
Configure channels based on sensor type (current/voltage) to avoid over-range use.
Version distinction:
Distinguished from IS220PAICH1A (non-secure PAIC Analog I/O package), YAIC focuses on secure loops, while PAIC is adapted to non-secure analog control.
V. Core Advantages
High security:
SIL2/3 compatible, meeting the compliance requirements of safety-critical scenarios.
High precision:
16-bit resolution + high isolation, ensuring the accuracy and stability of signal acquisition.
Easy integration:
Compatible with the Mark VIeS ecosystem, adapted to UCSC controllers and IONet networks, and supports upgrades of new and old systems.