Emerson KJ3202X1-BA1 DO 8-Channel 24 VDC High-Side
Emerson KJ3202X1-BA1 DO 8-Channel 24 VDC High-Side
Power Specifications
Local Bus Power
Bussed Field Power
Field Circuit
12 VDC at 150 mA
30 VDC at 3 A
30 VDC at 1 A/Channel, 3 A/Card
Environmental Specifications
Ambient
Temperature
Shock
Vibration
Airborne
Contaminants
Relative Humidity
Terminal Block key
Position -40°C to +70°C
10g ½ Sinewave for 11msec
1mm Peak to Peak from 2 to 13.2Hz;
0.7g from 13.2 to 150Hz
ISA-S71.04 –1985 Airborne
Contaminants Class G3
5 to 95% Non-Condensing IP 20 Rating
B6

KJ3202X1-BA1
Note: Refer to the product label for serial number
and location and date of manufacture.
Warning: This product has specific instructions for
installation, removal and operation in hazardous
areas. Refer to document 12P2046 “DeltaV™
Scalable Process System Zone 2 Installation
Instructions”. Other installation instructions are
available in the “DeltaV™ M-Series Hardware
Installation and Reference” manual.
Removal and Insertion
This unit cannot be removed or inserted with system
power energized unless the area is known to be
non‐hazardous and only one unit at a time may be
removed or inserted.
Non-sparking field circuits MUST be de-energized
before removing and inserting including the fused
terminal block.
A rotary keying system ensures compatibility
between I/O cards and terminal blocks after
installation is complete. The terminal block must
have the keys set for the I/O card with which it is
used.
Maintenance and Adjustment
This unit contains no user serviceable parts and
should not be disassembled for any reason.
Calibration is not required.