Uncategorized

Emerson DeltaV™ S series serial interface

Emerson DeltaV™ S series serial interface

Product Description

The S series serial interface can be connected to DeltaV™ systems and devices that support serial protocols, such as Modbus or Allen Bradley’s Data Bus Plus. Provide preloaded Modbus software drivers for S series serial interfaces. DeltaV serial interfaces can also be installed as redundant pairs for critical applications that require the highest reliability.

Specification

The number of serial interfaces

2

The number of datasets for each serial interface card

32 (16 per port)

Port type

RS232. RS422/485 half-duplex, RS422/485 full-duplex

Isolation

Each interface is isolated from the system and from one another. These interfaces should be externally grounded

Baud rate

300. 1200. 2400. 4800. 9600. 19200. 38400. 57600. 115200

Parity check

Even, odd, non-existent

Data bit

7 or 8

Stop position

1 or 2

Number of retries

0-255

Information timeout

100-25.500 milliseconds (increasing by 100 milliseconds)

Working temperature

-40 to 70 °C(-40 to 158 °F)

Storage temperature

-40 to 85 °C(-40 to 185 °F)

Relative humidity

5 to 95%, no condensation

Impact-resistant

A 10 g½ -sine wave lasts for 11 ms

Vibration

1mm peak value (from 2 to 13.2Hz), 0.7g(from 13.2 to 150 Hz)

PDP_DeltaV S-series Serial Interface

Features

Provide seamless information interfaces

Plug and play installation, saving money

Extend the service life of existing equipment

The interface automatically detects whether there are redundant power strips. The system automatically perceives the interface and regards it as a redundant pair

If a primary serial interface card fails, the system will automatically switch to the standby card without user intervention.