Emerson DeltaV™ S series 4-port FF fieldbus I/O

Emerson DeltaV™ S series 4-port FF fieldbus I/O

Product Description

FF fieldbus I/O is a modular subsystem that enables digital communication with field devices, enhancing your input/output capabilities and facilitating your access to more information about the process (rather than traditional I/O subsystems). This fieldbus I/O greatly improves the device diagnosis that affects your control strategy and can send device failure alerts to operators. If you wish to obtain a safe, efficient, economical and distributed process control system, use DeltaV™ FF fieldbus I/O.

Specification

Number of segments (number of ports

4

The number of on-site equipment

Each port IS 16(depending on the power consumption of the device and IS requirements)

The number of Ff function blocks

128 per card

Isolation

Each channel is isolated from the system and from one another. The factory test value is 1500 VDC

Nominal signal range (measurement range)

Fieldbus IEC 61158-2

The local bus current of each card (nominal 12 VDC)

It is generally 200 mA, with a maximum of 300 mA

Fieldbus power supply (Series 2 cards)

9 to 32 VDC, 12 mA per channel

Standard

IEC 61158 Data Link Layer

Atmospheric pollutants

ISA-S71.04-1985 Grade G3 conformal coating for air pollutants

Working temperature

-40 to 70 °C(-40 to 158 °F)

Storage temperature

-40 to 85 °C(-40 to 185 °F)

Relative humidity

5 to 95%, no condensation

Impact-resistant

A 10 g½ -sine wave lasts for 11 ms

Vibration

1 mm inter-peak value (from 5 to 13.2 Hz); 0.7g(from 13.2 to 150 Hz)

Features

Enhance I/O capabilities while reducing cabling costs

Due to the adoption of 4 ports, the occupied space is reduced

It has maximized the capabilities of smart devices

Redundant H1 cards enhance availability

Provide synchronous control

PDP_DeltaV S-series 4-port FOUNDATION Fieldbus IO