HIMA F60DIO24/1601 Safety-Related Controller
Configuring the System ID and the Connection Parameters
To configuring the system ID and the connection parameters
1. Select the resource in the structure tree.
2. Click the Online button located on the Action Bar or select Online on the context menu.
The System Login dialog box is displayed.
3. Click Search.
The Search per MAC dialog box appears.
4. Enter the MAC address valid for the controller – see the label on the housing – and click
Search.
In the dialog box, the values set for IP address, subnet mask and S:R:S are
displayed.
5. If the values for the project are not correct, click Change.
The Write via MAC dialog box appears.
6. Type correct values for the connection parameters and the S.R.S., and enter the access
data for a user account with administrator rigths valid on the controller. Click Write.
Connection data and S.R.S are configured and it is now possible to log in.
For further details, refer to the SILworX manual First Steps (HI 801 103 E).
Loading a Resource Configuration after a Reset
If the compact system is switched on with engaged reset key, it restarts and resets the
connections parameters and user account to the default values (only in case of a
controller). After a new restart with disengaged reset key, the original values are used.
If the connection parameters were modified in the user program, they can be configured in
the compact systems such as described in Chapter 8.2.6.
Logging in as Default User
After configuring the connection parameters and prior to loading the user program, the
default user (administrator with empty password) must be used in the following cases:
The password for the user account is no longer known.
A new user account should be used in the project.
To log in as default user
1. Select the resource in the structure tree.
2. Click the Online button located on the Action Bar or select Online on the context menu.
The System Login dialog box opens.
3. In the IP Address field, select the correct address or use the MAC address.
4. Enter Administrator in the User Group field.
5. Let the Password field empty or cancel the password.
6. Select Administrator in the Access Mode field.
7. Click Log-in.
SILworX isconnected to the HIMatrix controller with default user rights.
Use+A in the System Login dialog box to skip steps 4-6!
8.2.8
8.2.9
Loading a Resource Configuration from the PADT
Before a user program can be loaded with the connection parameters (IP address, subnet
mask and system ID) into the controller, the code must have been generated for the
resource, and ´the connection parameters for PADT and resource must be valid, see
Chapter 8.2.6.
To load a resource configuration from the PADT
1. Select a resource in the structure tree.
2. Click the Online button located on the Action Bar or select Online on the context menu.
3. In the System Login dialog box, enter a user group with administrator rights or write
access.
The Control Panel appears in the workspace and displays the controller state.
4. In the Online menu, select Resource Download.
The Resource Download dialog box appears.
5. Click OK to confirm the download.
SILworX loads the configuration into the controller.
6. Upon completion of the loading procedure, click the Resource Cold Start function on the
Online menu to start the user program.
After the cold start, System State and Program Status enter the RUN state.
The resource configuration is loaded from the PADT.
The Start, Stop and Load functions are also available as symbols on the Symbol Bar.
Loading a Resource Configuration from the Flash Memory of the
Communication System
If data errors were detected in the NVRAM thus causing the watchdog time to be exceeded,
it can be useful to load the resource configuration from the flash memory for the
communication system instead of from the PADT:
If the Control Panel (CP) is no longer accessible, the connection parameters for the project
must be reset in the controller, see Chapter 8.2.6.
If the controller adopts the STOP/VALID CONFIGURATION state after restarting, the user
program can again be started.
If the controller adopts the STOP/INVALID CONFIGURATION state after restarting, the
user program must be reloaded into the NVRAM.
Use the Load Configuration from Flash command to read a backup copy of the last
executable configuration from the flash memory for the communication system transfer it to
| HIMA | F8620/11 |
| HIMA | ELOPII |
| HIMA | F7131 981713102 |
| HIMA | F8621A 984862160 |
| HIMA | H51q-HS B5233-1 997105233 |
| HIMA | F3322 |
| HIMA | F7133 |
| HIMA | Z7136 |
| HIMA | Z7126 |
| HIMA | K9203A 996920360 |
| HIMA | F6705 |
| HIMA | BV7032-0,5 |
| HIMA | EABT3 B9302 997009302 |
| HIMA | F8627 |
| HIMA | F7533 |
| HIMA | F3231 |