Woodward SPM-D2-1010B/NYB 8440-2177
Product number: 8440-2177
Manufacturer product number: 8440-2177
Description: Woodward: SPM-D2-10/NYB, Dimensions: 144x72x122mm Input Voltage: 100V, 50Hz Output Contacts:
Discrete for Speed/Voltage Command: One Breaker Power Supply: 90…250 VAC/DC
The foil of the front plate is made of coated plastics. All keys have been designed as touch-sensitive membrane
switch elements. The display is a LC-display, consisting of 2 rows each with 16 characters, which are indirectly il
luminated red. Contrast of the display is infinitely variable by a rotary potentiometer on the left side.
Description Function
1 Bus CB Free Non-functional
2 Gen CB Free Enable CB
3 Automatic Automatic mode
4 CB close Close command to the CB issued
5 Synchroscope Display of phase position
6 f- Governor output: frequency lower (reduce speed)
7 f+ Governor output: frequency raise (increase speed)
8 V- Governor output: voltage lower (reduce excitation)
9 V+ Governor output: voltage raise (increase excitation)
10 Gen CB – ON Reply: CB is closed
11 Bus CB – ON Non-functional
Buttons
No. Description Function
12 Display Scroll display
12 Select Confirm selection
13 Digit Increase digit
14 Clear Acknowledge alarm
14 Cursor Shift input position one digit to the right
Others
No. Description Function
15 LC-Display LC-Display
Potentiometer Adjust LCD contrast
1 Bus CB Free
here: non-functional
Color: green
Enable mains circuit breaker
NOTE: This LED is non-functional, as this control is only designed to oper
ate one circuit breaker.
2 Gen CB Free
Color: green
Enable power circuit breaker
The LED “Gen CB Free” indicates that the power circuit breaker has been
enabled for operation. The status of the LED illuminates when the discrete
input “Enable/Release CB” is energized.
3 Automatic
Color: green
Automatic mode
The LED “automatic” is illuminated when the unit is in automatic mode. It
will turn off as soon as the control unit is switched to the configuration mode.
4 CB close
Color: green
CB close
The “CB close” LED illuminates when the unit outputs a closure command to
the power circuit breaker during synchronization. The “CB close” LED illu
minates when the relay “command: close CB” is energized.
5 LED-row: too fast
Color: red/yellow/green
Phase position / Synchroscope
The row of LEDs indicates the current phase relationship between the two
voltages indicated in the display. The green LED in the center of the 15 LEDs
indicates that the measured phase angle between the voltage systems is +/-
12 ° electrical. The phase position is only displayed if the controller is in au
tomatic mode and only if the systems U1 and U2 are within the following
limits:
Frequency ranges System U1 96 to 104% fN
System U2 88 to 112% fN
Voltage ranges System U1 85 to 112% VN
System U2 75 to 115% VN
The synchroscope LEDs can move in two directions:
left right . If the LEDs illuminate from left to right, the generator (variable
system) frequency is higher than the mains or reference voltage
system (i.e. the generator or the variable system has a frequen
cy of 60.5 Hz and the mains is 60 Hz).
right left . If the LEDs illuminate from right to left, the generator (variable
system) frequency is lower than the mains or reference voltage
system (i.e. the generator respectively the variable system has a
frequency of 59.5 Hz and the mains is 60 Hz).
| GEC ALSTHOM | MCGG52H1CB0753C |
| GEC ALSTHOM | MVAJ13D1GB0780A |
| GEC ALSTHOM | MVAJ23B1AB0757B |
| GEC ALSTHOM | MCGG22D1CB0753C |
| GEC ALSTHOM | MCHN02D1AB0004A |
| GEC ALSTHOM | MVAX31C1DF0754A |
| GEC ALSTHOM | MVAX12B1DA0753A |
| GEC ALSTHOM | MCHN02D1AB0005A |
| GEC ALSTHOM | MVUA11B1BD0784B |
| GEC ALSTHOM | MVAA14B1AA0785C |
| GEC ALSTHOM | 3BE101 |
| GEC ALSTHOM | MVTT14B1BA0773C |