Woodward MFR500-6M/WK0400 + DPC USB 8444-1070
Undervoltage (Level 1 & 2) ANSI# 27
Voltage is monitored according to how the parameter “Voltage
measuring” (parameter 1851 Ä p. 41) is configured. This controller
provides the user with two alarm levels for undervoltage. Both
alarms are definite time alarms.
Monitoring for undervoltage faults is performed in two steps.
The diagram listed below shows a frequency trend and the associ
ated pickup times and length of the alarms.
4.4.3 Overfrequency (Level 1 & 2) ANSI# 81O
This controller provides the user with two alarm levels for overfre
quency. Both alarms are definite time alarms.
Monitoring for overfrequency faults is performed in two steps.
The diagram listed below shows a frequency trend and the associ
ated pickup times and length of the alarms.
Underfrequency (Level 1 & 2) ANSI# 81U
This controller provides the user with two alarm levels for underfre
quency. Both alarms are definite time alarms.
Monitoring for underfrequency faults is performed in two steps.
The diagram listed below shows a frequency trend and the associ
ated pickup times and length of the alarms.
4.4.5 Positive Load (Level 1 & 2) ANSI# 32
The power is monitored depending on parameter “Voltage meas
uring” (parameter 1851 Ä p. 41) and parameter “Current meas
uring” (parameter 1850 Ä p. 40).
If the single- or three-phase measured real power exceeds the
configured limit, the alarm will be issued.
Both alarm limits may either be positive or negative.
Description
If the monitored load exceeds the threshold value for the delay time config
ured here, an alarm will be issued.
Notes
If the monitored load falls below the threshold (minus the hysteresis) before
the delay expires the time will be reset.
The relay configured here is activated if the respective monitoring functions
triggers. If “None” is configured here, no relay is activated in this case.
Notes
Whether the relay is energized or de-energized depends on the configuration
of the relay function (parameter 6920 Ä p. 43 , 6921 Ä p. 43. 6922 Ä p. 43
and 6923 Ä p. 43).
Negative Load (Level 1 & 2) ANSI# 32R/F
General notes
The power is monitored depending on parameter “Voltage meas
uring” (parameter 1851 Ä p. 41) and parameter “Current meas
uring” (parameter 1850 Ä p. 40).
If the single- or three-phase measured real power is below the con
figured limit, the alarm will be issued.
Both alarm limits may either be positive or negative.
The negative load monitoring follows the same principle as the
positive load monitoring, but triggers when the value falls below the
threshold.
Unbalanced Load (Level 1 & 2) ANSI# 46
Unbalanced load is monitored according to how the parameters
“Voltage measuring” (parameter 1851 Ä p. 41), “Current meas
uring” (parameter 1850 Ä p. 40) and “Phase rotation” (parameter
3954 Ä p. 41) are configured.
The unbalanced load alarm is a phase imbalance alarm. Unbal
anced load is determined by calculating the negative sequence
component of a three phase system. This value is derived from the
three current components and the angle between them. Unbal
anced load monitoring is only active if “Current measuring” (param
eter 1850 Ä p. 40) is configured to “L1 L2 L3” and “Voltage meas
uring” (parameter 1851 Ä p. 41) is either configured to “3Ph 4W”
or “3Ph 3W”. The threshold is defined as the percentage of that
value relative to the nominal current. The protective function is trig
gered if this percentage value is exceeded
| H0NEYWELL | 05701-A-0326 |
| H0NEYWELL | 05701-A-0301 |
| H0NEYWELL | 05701-A-0329 |
| H0NEYWELL | 05701-A-0502 |
| HAAS | 3283C Rev W |
| HAAS ROTARY CONTROL | 65-4170 REV E |
| HANRUN | HR871137C(MVME6100 |
| HARDY | HI2151/20WC |
| HARMONIC | HA-600-4 |
| HARMONIC | SC-510-5-230-S0 |
| HARTING | 09061487901 |
| HARTING | 09051486921 |
| Hartmann & Braun | P.11471-0-1011015 TEU 471 |
| HB | CONTRANS T TEU471 |
| HEIDENHAIN | ROD700-18000 |
| HEIDENHAIN | IK340 |
| HILSCHER | CIF80-PB |
| HIMA | K9203 |
| HIMA | F8650X |
| HIMA | F3236 |
| HIMA | F3330 |