Woodward MFR300-71M/K42 8444-1104
Woodward MFR300-71M/K42 8444-1104
Phase Shift
General notes
A vector/phase shift is defined as the sudden variation of the voltage curve which may be
caused by a major source load change.
The unit measures the duration of a cycle, where a new measurement is started with
each voltage passing through zero. The measured cycle duration will be compared with
an internal quartz-calibrated reference time to determine the cycle duration difference of
the voltage signal.
A vector/phase shift as shown in ╚═▷ Fig. 38 causes a premature or delayed zero passage.
The determined cycle duration difference corresponds with the occurring phase shift
angle.
The monitoring may be carried out three-phase or one/three-phase. The monitoring can
be configured in different ways. The vector/phase shift monitor can also be used as an
additional method to decouple from the grid. Vector/phase shift monitoring is only
enabled after the monitored voltage exceeds 50% of the PT secondary rated voltage
Voltage is monitored depending on parameter “Monitoring” (param
eter 8806 Ä p. 64). This function allows the monitoring of the
voltage quality over a longer time period. It is realized as a 10
minute moving average. The function is only active, if the fre
quency is larger than 60 % of the nominal frequency. If “Voltage
measuring” (parameter 1851 Ä p. 41) is configured to a three
phase measurement, the slow voltage increase alarm is monitoring
the individual three-phase voltages according to parameter “AND
characteristics”
n case of undervoltage some grid codes require a special moni
toring function to avoid the import of inductive reactive power at the
interchange point. The QV monitoring is a function of voltage and
reactive power. To prevent malfunction, a “Minimum current”
(parameter 3287 Ä p. 67) must be configured.
QV monitoring is triggered if the following conditions are fulfilled:
(Refer to Fig. 38 for details)
n QV monitoring is configured to “On” (parameter 3292 Ä p. 67)
n Measured reactive power is higher than the configured “Reac
tive power threshold” (parameter 3291 Ä p. 67)
n Measured average current is higher than the configured “Min
imum current” (parameter 3287 Ä p. 67)
n Measured voltages are below the configured “Limit under
voltage” (parameter 3285 Ä p. 67)
As a result Timer 1 and Timer 2 are starting. If the delay time
“Delay step 1” (parameter 3283 Ä p. 67) has exceeded, the speci
fied relay for step 1 is energized. If the delay time “Delay step 2”
(parameter 3284 Ä p. 67) has exceeded, the specified relay for
step 2 is energized.
| HIMA | F8651X |
| HIMA | F6214 |
| HIMA | F6215 |
| HIMA | K9202 |
| HIMA | F3DIO20/802 |
| HIMA | X-DI3201 985210201 |
| HIMA | X-DO2401 985210203 |
| HIMA | 80105 984080105 |
| HIMA | F3DIO20/802 982200442 |
| HIMA | F35 |
| HIMA | Z7116/3236/C5 |
| HIMAtrix | F3001020 |
| HIMAtrix | F2DO801 |
| HIMAtrix | F3DIO20/802 |
| HIMAtrix | F30 010 20 OS-REV.V6.46/V11.28 |
| HINDS | DPEM-460A 4022.455.16351 |
| Hirschman | MM2-4TX1 |
| HIRSCHMANN | MS20-1600SAAEHC07.1.01 |
| HIRSCHMANN | MINI-UTDE 10 BASE-T |
| Hirschmann | MM20-Z6Z6Z6Z6SBH |
| Hirschmann | MS4128-L2P |
| Hirschmann | MM3-2FXM2/2TX1 |
| Hirschmann | MS4128-L3P |
| HITACHI | 2-822037-A |