Woodward MFR300-71M 8444-1063
MFR300-71M 8444-1063
The MFR 300 is a measuring transducer for
monitoring single- and three-phase power
systems. The MFR 300 has both voltage and
current inputs for measuring an electrical power
source. A digital processor makes it possible to
accurately to measure true RMS values,
regardless of harmonics, transients or
disturbing pulses. The primary measured and
calculated values are transmitted via CANopen
/ Modbus protocol to a supervisory control
system.
The MFR 300 performs monitoring functions for
mains decoupling, including four freely
configurable time-dependent undervoltage
monitoring functions for FRT (fault ride
through).
The primary measured values of voltage and
current are used to calculate the real, reactive,
and apparent power and the power factor
(cosphi) values.
The list of measured values includes
Measured
Voltage
Wye: VL1N / VL2N / VL3N
Delta: VL12 / VL23 / VL31
Frequency fL123
Current IL1/IL2/IL3
Calculated
Average voltage VØL123 / Vmin / Vmax
Average current IØL123 / Imin / Imax
Real power Ptotal / PL1 / PL2 / PL3
Reactive power Qtotal
Apparent power Stotal
Power factor (cosφL1)
Active energy kWhpositive/negative
Reactive energy kvarhleading/lagging
Features
3 true RMS voltage inputs
3 true RMS current inputs
Class 0.5 accuracy for voltage,
frequency and current
Class 1 accuracy for real and
reactive power or energy
Configurable trip/control setpoints
Configurable delay timers for
individual alarms (0.02 to 300.00 s)
4 configurable relays (change-over)
1 “Ready for operation” relay
Switchable relay logic
2 kWh counters (max. 1012 kWh)
2 kvarh counters (max. 1012 kvarh)
CANopen / Modbus communication
Configurable via CAN bus / RS-485
/ Service Port (USB/RS-232)
24 Vdc power supply
Protection (all) ANSI #
Over-/undervoltage (59/27)
Over-/underfrequency (81O/U)
Voltage asymmetry (47)
Overload (32)
Positive/negative load (32R/F)
Unbalanced load (46)
Phase shift (78)
Overcurrent (50/51)
df/dt (ROCOF)
Ground fault
QV monitoring
Voltage increase
Freely configurable time-dependent
undervoltage monitoring for:
o FRT (fault ride-through)
| GE | IS200TSVCH1AED |
| GE | IS200JPDMG1ACC S1AT005 |
| GE | IC800SSI228RD2-EE |
| GE | DS200DCFBG2BNC |
| GE | DS200DCFBG2BNC MRP445970 |
| GE | CI871AK01 3BSE092693R1 |
| GE | D20EME10BASE-T 820-0474 |
| GE | IS420UCSCH1A-F.V0.1-A |
| GE | 369-HI-R-0-0-0-0-E |
| GE | 369-HI-R-M-0-0 |
| GE | AL122 |
| GE | D20C PANEL |
| GE | D20C TERMINATION |
| GE | TED134050WL |
| GE | 369B1860G0030 |
| GE | 208D9845P0008 |
| GE | 369B1844G5004 |
| GE | 369B1859G0021 |