easYgen-3500XT-P2-K58 8440-2318
When the engine is operated at idle speed, undervoltage, underfre
quency, and underspeed monitoring as well as the monitoring of
the flexible limits 33 through 40 are not performed.
This function allows for a controlled operation of an engine without
alarm messages at a lower speed (below the configured under
speed monitoring values) for e.g. a warm-up operation with low
emission.
The frequency controller output does not control the idle speed; it
will remain in initial state position. The GCB cannot be closed in
idle mode.
A message may be output to a relay here using the LogicsManager
(Idle mode is active, command variable 04.15), e.g. as a signal for
a speed controller. The display indicates “Idle run active” during
idle mode.
Parameter CL Setting range
[Default]
Description
12570 Auto idle mode 2 Determined by
LogicsManager
86.20
[(0 & 1) ≥1 0]
= 15719
Once the conditions of the LogicsManager have been fulfilled the engine will
be operated in idle mode automatically for the configured time during start-up.
Monitoring is limited as described above.
This function may always be configured to “1” for example.
Notes
For information on the LogicsManager and its default settings see Ä Chapter
9.3.1 “LogicsManager Overview” on page 860.
12550 Constant idle
run
(Continuous idle
mode)
2 Determined by
LogicsManager
86.14
[(0 & 1) & 0]
= 10713

8440-2318
As long as the conditions of the LogicsManager have been fulfilled the engine
will be continuously operated in idle mode. Monitoring is limited as described
above. A key switch via a DI may be configured here for example.
Notes
The idle mode is blocked if the GCB is already closed.
For information on the LogicsManager and its default settings see Ä Chapter
9.3.1 “LogicsManager Overview” on page 860.
Parameter CL Setting range
[Default]
Description
3328 Automatic idle
time
(Time for auto
matic idle mode)
2 1 to 9999 s
[30 s]
The automatic idle mode is active for the time configured here. Monitoring is
limited as described above during this time.
3329 During emer
gency / critical
(Idle mode pos
sible during
emergency /
critical opera
tion)
2 Yes If an emergency or critical operation is enabled, the engine will go to rated
speed only after completing the configured idle mode.
[No] If an emergency or critical operation is enabled, no idle run will be performed.
The engine will go directly to rated speed
The generators are paralleled together by closing their circuit
breakers during the engine start sequence. Then after a certain
speed is achieved the voltage regulators are enabled and the gen
erators will produce voltage. The run-up synchronization method is
used to get several synchronous generators onto load in a very
short time. This time is determined by the engine start time and the
AVR on-excitation
Programmable–The discrete input has been assigned a default function
using either the LogicsManager or preconfigured alarms
such as “emergency stop”.– The following sections describe how these functions are
assigned.– The function of a discrete input can be changed if required.– The following description of the inputs, labeled with “pro
grammable”, refers to the preconfiguration.
n Fixed– The discrete input has a specific function that cannot be
changed depending upon the configured application mode
| ABB | 500BOM01 1MRB150023R0002 |
| ABB | 500MTM02 1MRB150020R0712 1HDF 930512 X010 |
| ABB | 500MTM02 1MRK001967-AA 1HDF 930512 X010 |
| ABB | 500MTM02 1MRB150020R1102 1HDF 930512 X010 |
| ABB | 500AIM02 1MRB150022R001 1HDF 930412 X010 |
| ABB | 500AIM02 1MRB150022 R0002Y 1HDF 930412 X010 |
| ABB | 500AIM02 1MRB150022 R0002 1HDF 930412 X010 |
| ABB | 500PSM02 1MRB150015R1 AD-272.100.20-01 AZ:C |
| ABB | 500PSM03 1MRB 150038 R1 894-030375D 136-011100H |
| ABB | 500BIM01 1MRB160024R0002 |
| ABB | 500BIM01 1MRB150024R0002 |