Woodward easYgen-2300-1/P1 8440-2122
IMPROVE YOUR SYSTEM EFFICIENCY
This compact and aff ordable genset control
and protection package allows you to defi ne
how your gensets are brought on- and off -line to
support changing load demands even with a mix
of diff erent-sized engines
New cost optimal easYgen-2300
with direct connection to speed control and voltage regulator:
Load sharing of up to 16 gensets in island mode
Parallel interconnection of a single genset to the grid*
Easy customization of control commands with
Woodward‘s LogicsManagerTM
Support of all standard interfaces
(e.g., CAN/J1939. RS-485)
Ethernet, Profi bus and remote communication through
dedicated gateways
and many more ..
* fi xed power import/export
FEATURE OVERVIEW Package P1 Package P2
easYgen-2300
Discrete Inputs 8 8
Relay Outputs 6 6
Analog Inputs 3 3
Analog Outputs 2 2
CANbus Interfaces 1 2
RS-485 Interface 1
RS-232 Interface 1 1
allel operation and monitors a series of subordinate mains protec
tion thresholds. If a threshold is exceeded, the easYgen initiates a
breaker opening and separates the generator(s) from the mains at
the defined breaker.
The following thresholds are monitored:
n Overfrequency level 2 ( Ä Chapter 4.4.2.3 “Mains Overfre
quency (Level 1 & 2) ANSI# 81O” on page 138)
n Underfrequency level 2 ( Ä Chapter 4.4.2.4 “Mains Underfre
quency (Level 1 & 2) ANSI# 81U” on page 139)
n Overvoltage level 2 ( Ä Chapter 4.4.2.5 “Mains Overvoltage
(Level 1 & 2) ANSI# 59” on page 140)
n Undervoltage level 2 ( Ä Chapter 4.4.2.6 “Mains Undervoltage
(Level 1 & 2) ANSI# 27” on page 141)
n Mains phase shift / df/dt (ROCOF) ( Ä Chapter 4.4.2.10
“Change Of Frequency” on page 149)
If one of these protective functions is triggered, the display indi
cates “Mains decoupling” (the logical command variable “07.25”
will be enabled) and the active level 2 alarm.
When the mains decoupling function detects a breaker open
failure, the according breaker alarm will be triggered as long the
monitoring function is activated. Additionally in cases where the
decoupling mode has to change over to the other breaker,
(GCB®MCB, MCB®GCB), the alarm text “Decoupling
GCB«MCB“ is indicated. The breaker open alarm already occurs
after the mains decoupling feedback delay (refer to ID
| ABB | PM858-C 3BSE093350R1 |
| ABB | XVC768101 3BHB007211R101 |
| ABB | XVC770AE 3BHE006414R0001 |
| ABB | LTC391AE01 HIEE401782R0001 |
| ABB | XVC770BE102 3BHE021083R0102 |
| ABB | TB840A 3BSE037760R1 |
| ABB | REU615 |
| ABB | S-113H 3BHB018008R0003 D1961SH45TS02 D1031SH45TS02 3BHL000986P0006 |
| ABB | PFSK152 3BSE018877R1 |
| ABB | S-093H 3BHB009885R0004 |
| ABB | REU615E_D HBUAEAADNCA1BNN1XD |
| ABB | COM0034 2RCA023019A0004C |
| ABB | L003748-AR 3BSX108237R300 |
| ABB | REF615 |
| ABB | RED615 |
| ABB | REM611 |