Woodward -5/P2 8440-1857 Genset Control
The Power Factor Characteristic function is adapting the reactive
power flow between generator and mains to support a dynamic
stabilization of the mains. Some network provider prefer therefore
a power factor control over real power PF(P) (see chapter
Ä Chapter 4.5.12.6.2.1 “Power factor characteristic PF(P) ”
on page 279 for more details).
Power factor characteristic PF(P)
A method to support the mains is to feed different reactive power
values into the grid in relation to the own active power value. The
reactive power is defined through a power factor setpoint for the
generator. This can be defined in characteristic curve
The linear characteristic is defined by two points (① & ②). The
power factor corresponding to this characteristic is available as
data source 05.29 in the Analog Manager
The easYgen performs proportional load and/or var sharing. This
means each generator will share the load at the same percentage
level of the generator rated power when paralleled against the
mains, in an isolated operation with multiple generators paralleled,
or when re-synchronizing the common bus to the mains
Mains Parallel Operation With Mains Interchange Real Power Control (Import/Export)
The easYgen controllers maintain the real load level on the individ
ually controlled generators at a level so that the real power setpoint
at the mains interchange remains at the configured setpoint. The
real power setpoint for the mains interchange must be configured
identically for each easYgen
system via a CAN bus. This enables the controllers to adjust the
real power generated by the generator while remaining within the
rated power of the generator. A smaller generator will contribute
less real power as compared to a large generator, but they will
both be utilized to the same capacity factor. An example of this
would be a 100 kW generator with a configured 1000 kW generator
and a mains interchange of 825 kW. The 100 kW generator would
contribute 75 kW and the 1000 kW generator would contribute
750 kW or both generators would be at 75 % of their rated
capacity.
| ABB | PM802F 3BDH000002R1 |
| ABB | PPD113B03-26-100110 3BHE023584R2634 |
| ABB | REM620A_F NAMBBABA33E5BNN1XF |
| ABB | 3BHE019719R0101 GVC736BE101 |
| ABB | 5SHY4045L0003 3BHB021400 3BHE019719R0101 GVC736BE101 |
| ABB | UFC721AE101 3BHB002916R0101 |
| ABB | UBC717AE01 HIEE300927R0101 |
| ABB | CI930F 3BDH001010R0005 |
| ABB | KUC720AE01 3BHB003431R0101 3BHB000652R0101 |
| ABB | KUC720AE101 3BHB003431R0101 3BHB000652R0101 |
| ABB | 3BHE004573R0143 UFC760BE143 |
| ABB | UFC765AE102 3BHE003604R0102 |
| ABB | XVC769AE101 3BHE006373R0101 |
| ABB | UFC718AE01 HIEE300936R0101 |
| ABB | PCD235B101 3BHE032025R0101 |
| ABB | UNITROL 1005-0011 ECO 3BHE043576R0011 |
| ABB | SAM3.0 |
How the reactive power handling is executed depends the PF/kvar
setpoint mode. Two setpoints (5743 Ä p. 278 and 5744 Ä p. 278)
are available. Each setpoint allows the modes:
n Gen PF
n Mains PF
n Mains Import kvar
n Mains export kvar
In PF modes the reactive load sharing is not performed when
operating in parallel with the mains. Reactive power control will be
defined by the configured power factor setpoints (5620 Ä p. 278 or
5621 Ä p. 278) of the individual controllers. If the power factor con
troller setpoint is configured as +0.950. the easYgen will propor
tionally share the real load with all generators in parallel with the
mains while controlling the reactive power at a 0.95 inductive (lag
ging) power factor regardless of the what power factor the mains is
operating at.
The parameter “Active power Load share factor” (param
eter 5530 Ä p. 285) can be used now to define the priority of the
real power sharing reference variable (real power at interchange).
A higher configured percentage influences the control more
towards maintaining the real power setpoint for the interchange. A
lower configured percentage influences the control more towards
maintaining real power sharing between units.
In kvar modes the reactive load sharing is performed when oper
ating in parallel with the mains. Mains import/export kvar control at
the interchange point will be determined by the configured int. kvar
setpoints (5745 Ä p. 278 or 5746 Ä p. 278) of the individual con
trollers.
Isolated Operation In Parallel
The easYgen controllers maintain the voltage and frequency of the
individually controlled generators at a constant level. This makes it
imperative that the voltage and frequency setpoints are configured
identically for each easYgen