Woodward

Control Panel 9907-2024 Woodward

Control Panel  9907-2024 Woodward

Unpacking

Before handling the control, read the “Electrostatic Discharge Awareness”

precautions on page iii. Be careful when unpacking the electronic control. Check

the control for signs of damage such as bent or dented panels, scratches, and

loose or broken parts. If any damage is found, immediately notify the shipper.

Power Requirements

The 2301A control requires a voltage source of 18 to 40 Vdc, 90 to 150 Vdc, or

88 to 132 Vac for operating power (15 W). If a battery is used for operating

power, an alternator or other battery charging device is necessary to maintain a

stable supply voltage.

Location Considerations

This product is intended for installation in a “closed electrical operating

area” or in a closed industrial control cabinet. Consider these requirements

when selecting the mounting location:

Adequate ventilation for cooling

Space for servicing and repair

Protection from direct exposure to water or to a condensation-prone

environment

Protection from high-voltage or high-current devices, or devices which

produce electromagnetic interference

Avoidance of vibration

Selection of a location that will provide an operating temperature range of  –40 to +70 °C (–40 to +158 °F)

The control must NOT be mounted on the engine.

Electrical Connections

External wiring connections and shielding requirements for a typical control

installation are shown in the plant wiring diagram (Figure 1-2). These wiring

connections and shielding requirements are explained in the balance of this

chapter.

Shielded Wiring

All shielded cable must be twisted conductor pairs. Do not attempt to tin (solder)

the braided shield. All signal lines should be shielded to prevent picking up stray

signals from adjacent equipment. Connect the shields to the control terminals as

shown in Figure 2-1 and in the plant wiring diagram (Figure 1-2). Wire exposed

beyond the shield should be as short as possible, not exceeding 50 mm (2

inches). The other end of the shields must be left open and insulated from any

other conductor. Do not run shielded signal wires with other wires carrying large

currents. See Woodward application note 50532. EMI Control for Electronic

Governing Systems, for more information.

Where shielded cable is required, cut the cable to the desired length and prepare

the cable as instructed below and shown in Figure 2-1.

Strip outer insulation from BOTH ENDS, exposing the braided or spiral

wrapped shield. DO NOT CUT THE SHIELD.

Using a sharp, pointed tool, carefully spread the strands of the shield.

Pull inner conductor(s) out of the shield. If shield is the braided type, twist to

prevent fraying.

Remove 6 mm (1/4 inch) of insulation from the inner conductor(s).

Connect wiring and shield as shown.

In installations with severe electromagnetic interference (EMI), shielded wire run

in conduit, double shielded wire, or other precautions may be required. Contact

Woodward for more information.

Setting Speed Range

The speed range to be selected is determined by the maximum desired prime

mover speed. Calculate the frequency of the speed sensor signal at the

maximum prime mover speed by multiplying the gear speed in revolutions per

minute times the number of teeth on the speed sensing gear and dividing by 60.

Select the lowest speed range which contains this maximum speed sensor

frequency.

5009XT with 2 120 V AC/DC PS

8262-1141

5009XT with 2 220 VAC PS

8262-1142

5009XT with 2 24 VDC PS

8262-1143

Accessories:

17” TouchPanel OCP – Includes RemoteView Software Program

8269-1073

RemoteView – Software License

8928-5311

Actuator Module Kit (2 2-Chan Act Modules, 2 Cables, 1 FTM)

8928-7574

Kit 5009XT Optional Analog/IO/FTM/Cable

8928-7575

Control Cabinet- 5009XT MICRONET + PROTECH-GII, (HV/HV, VOTED) +

220VAC TMR PS+ INTEG ACT KIT

9907-2024

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注