UniOP CP02F-02. CP02R-04
UniOP CP02F-02. CP02R-04
Compact HMI devices with 9 function keys/numerical keypad and display with 20 characters per line.
Show up to 2 or 4 rows, 20 characters of
information
• Choice of Vacuum Fluorescent or
Monochrome LCD
• Up to 16 user programmable function keys
with slide-in legends and LED indicators
• Connection to industrial bus systems and
Ethernet with optional modules
• IP65 front panel protection
• Version with extended operating temperature
available
The CP02 HMI panels are part of the UniOP family of entry-level products. They support the rich
common functionality of the UniOP operator panels:
• Powerful and intuitive programming with
the UniOP Designer 6 software
• Support of more than 130 communication
drivers for industrial devices
• Optional modules for fieldbus systems
(Profibus DP, CANopen, DeviceNet,
Interbus) and Ethernet. Ethernet modules
allow connection to field devices as well
as programming the HMI from Designer.
• Dual-driver communication capability
• Display dynamic data in numerical and
text formats
• Recipe data storage. Recipe data can be
transferred to an host computer using the
Ethernet connection.
• Multilanguage applications. The number
of runtime languages is limited only by the
available memory. All text information in
the application can be exported in Unicode
format for easier translation.
• Powerful macro editor to configure
touchscreen operation
• Alarms and historical alarm list. Alarm
and event information can be printed or
tn227-0.doc – 3.11.2005
UniOP CP02F-02. CP02R-04
transferred to an host computer using the
Ethernet connection.
• Eight level password protection.
• Report printing to serial printer. Reports
are freely configurable using Designer.
• Ethernet-based UniNet network to share
data between UniOP HMIs and to serve
data using UniNet OPC Server.
Technical Data
Display
Type CP02F-02 VFD
CP02R-04 LCD
Rows/columns CP02F-02 2/20
CP02R-04 4/20
Character height 5 mm
User definable
characters
CP02F-02 –
CP02R-04 8
Backlight CP02F-02 –
CP02R-04 LED 100K hour typ.
Contrast regulation CP02F-02 –
CP02R-04 software
Memory
User memory 512 KB
User memory
expansion
512 KB
Front panel
Function keys 16 with slide-in legends in
common with numerical
keypad
System keys 7
User LED’s 16
System LED’s 1
Interfaces
PC/Printer port Yes
PLC port RS-232. RS-485. RS-422. 20
mA Current Loop
Aux port (fieldbus and
Ethernet)
Yes, with optional modules
Serial programming
speed
9600 – 38400 bps
Functionality
Graphics –
Dual driver capability Yes
Recipe memory 16 KB
UniNet network Client/Server
Alarms 1024
Event list 256
Password Yes
Hardware RTC Yes, battery backed
Screen saver –
Battery 3 V 270 mA Lithium, non
rechargeable, user
replaceable, model CR2430.
Replace with same component
or equivalent compatible with
the operating temperature of
the product.
Ratings
Power supply voltage 18 – 30 VDC
Current consumption 0.3 A at 24 VDC
Fuse 2A T
Weight 1.1 Kg
Environmental
Conditions
Operating temperature-0045 0 to 50 °C -00A8 -30 to 60 °C (note 1)
Storage temperature -0045 -20 to 70 °C -00A8 -40 to 70 °C
Operating and storage
humidity
5 – 85 % RH non-condensing
Protection class IP65 (front panel)
Dimensions
Faceplate LxH 138×186 mm (5.43×7.32“)
Cutout AxB 117×176 mm (4.61×6.50“)
Cutout depth (type
0045 and 00A8)
74 mm (2.92”)
Max panel thickness 5 mm (0.2”)
Note 1: the operating temperature of the version –00A8 is subject to the following restrictions:
a) the panel can be operated in the temperature range -30°C to -20°C without damages but the display
response may be very slow.
b) regular display response requires a temperature of -20°C or higher
c) powering the product for a period of at least 25 minutes at an enviroment temperature of -30°C
will ensure that the internal temperature will increase to -20°C and then proper operation of the
display will be ensured.
Important note:
operating at extreme temperatures it is very important to ensure that the Relative Humidity ratings are
not exceeded.
The product is designed for installation in industrial environments in compliance with the regulations:
Emitted interference EN 61000-6-4. 2001
Noise immunity EN 61000-6-2. 2001
CP02F-02-0045
CP02R-04-0045
CP02R-04-00A8
Entry-level HMI with VFD display
Entry-level HMI with LCD display
Entry-level HMI with LCD display. Extended operating temperature
range.