ABB 500TRM02 1MRB150011R0001 Terminal/Input-Output Board

The ABB 500TRM02 (Part Number: 1MRB150011R0001) is a high-performance Transformer Module (or Terminal/Input-Output Board) belonging to the ABB REB500 busbar protection family.

It acts as the physical interface for analog signals, specifically designed to convert and isolate high-level current and voltage signals from primary equipment into low-level signals for digital processing.

Technical Parameter Table

Parameter Specification
Model Number 500TRM02
Order Code 1MRB150011R0001
Function Analog Input Transformer / Signal Conditioning
Number of Channels Typically 10 to 12 Analog Inputs (CT/VT)
Rated Input Current 1A or 5A (Software/Hardware selectable)
Rated Input Voltage 100V – 120V AC (Nominal)
Isolation Voltage 2.5 kV AC (between primary and secondary)
Burden < 0.1 VA per channel (Current); < 0.25 VA (Voltage)
Operating Temperature -25°C to +60°C
Weight ~0.50 kg

Product Advantages and Features

High-Accuracy Isolation: Uses high-grade magnetic transformers to ensure a clean, isolated signal, protecting sensitive CPU boards from high-voltage transients.

Mill-Duty Robustness: Designed with a ruggedized housing to withstand the vibration, dust, and temperature extremes of power plants and petrochemical facilities.

Fast Sampling Integration: Optimized to support the REB500’s sub-cycle tripping speed requirements by providing zero-phase-shift signal conversion.

Versatile Signal Handling: Can be configured to handle both Current Transformer (CT) and Voltage Transformer (VT) inputs in a single module.

Modular Design: Facilitates easy hot-swapping or system expansion in 19-inch rack-mounted protection schemes.

Application Cases

Substation Automation: Acts as the primary analog interface for REB500 bay units, measuring feeder currents for differential protection.

Transformer Protection: Monitoring currents at the primary and secondary ends of power transformers to detect internal faults.

Load Management: Provides real-time analog data to SCADA systems for power dispatching and grid stability monitoring.

Retrofit Projects: Used to bridge the gap between existing analog CT/VT wiring and modern digital IEC 61850 protection systems.

Installation and Maintenance

Installation

CT Short-Circuiting: Critical! Never disconnect the current transformer wiring from the module while the primary circuit is energized. Always short-circuit the CT secondary terminals first to avoid lethal high voltages.

Grounding: Ensure the M8 grounding screw on the module or the subrack is connected to the station ground to maintain the integrity of the isolation barrier.

Terminal Tightness: Check that all screw terminals are torqued correctly; loose connections on CT circuits can lead to arcing and module failure.

People who have purchased this product have also inquired about…

ABB 3HAC9710-1
ABB 3HAC5566-1
ABB 3HAC10847-1
ABB 3HAC6157-1
ABB 3HAC6428-1/04
ABB 3HAC7681-1
ABB 3HAC7344-1
ABB 3HAC5497-1
ABB 3HAC5518-1
ABB 3HAC5498-1
ABB 3HAB9271-1/01B
ABB 3HAB8859-1/03A
ABB DSQC346B
ABB DSQC509
ABB DSQC504
ABB BC25
ABB S503X
ABB 3HAC0977-1

Maintenance

Phase Accuracy Check: During scheduled outages, perform a secondary injection test to ensure the 500TRM02 is converting values within its ±0.5% accuracy range.

Visual Inspection: Check for signs of localized overheating (discoloration) near the input terminals, which may indicate a high-burden or poor connection.

Cleaning: Use a lightly moistened cloth with mild detergent to clean the front panel. Do not allow liquids to enter the module casing.

Other Models in the Same Series

Model    Description

500TRM01    Standard Analog Input Transformer (Earlier Revision)

500TRM03    Specialized high-current version for industrial drives

500BIO01    Binary Input/Output interface module

500CPU05    Central Processing Unit that processes the TRM signals

500CUM05    Central Unit Management Module

Peer Tip: When replacing a 500TRM02. double-check your CT Ratio settings in the HMI.

If the new module is installed but the settings are not refreshed, you may receive “Differential Current Alarm” errors due to scaling mismatches.