METSO A413313 Valmet Module
Typical application template structure
Typical calculated characters vs faults
© Valmet |
Monitoredphenomena Character
ISO/DIN machinevibration severity (load,
stress)
Vibrationvelocity rms, from frequency range 10
Hz –1 kHz
Faultscreating high frequency vibration or
impacts , like;-Rolling element bearing fault-Lack of lubrication-Cavitation
Coupling fault
Rolling element bearing fault impulses
Vibrationacceleration rms frequency range 1
kHz -10 kHz
Envelope signal peak and FFT rms
Acceleration peak value
Vibration velocity rms
Frequency range 5-20xrpm (rotation
frequency)
Unbalance and alignment Vibration velocity rms
1xrpm + 2xrpm
Gearbox faults Vibration velocity in gear mesh frequency
Detailed diagnostic Signal, FFT, envelope signal and FFT, STA
analysis
Valmet DNA Operate, to see total view
Mix trends (vibrations, process parameters)
Condition monitoring results and process
data can be viewed and analysed in same
trends using DNA history tools
This will enable maintenance engineer to
simultaneous viewing of vibrations and
related process values in the same trends
This can be very valuable to optimize
machine operation, think about cases like;
Fan vibration versus motor power or air
flow
BFP vibration versus steam / casing heat
up curve (changes in case shape)
Pump vibrations versus pump pressure /
water flow etc
Vector storing principle
To have good history without excess load into database =data
management in SQL database
Vectors (signal, spectra and equal) are stored in 3 levels– Short history– Medium history (vectors removed from short history based on delta-time between
them)– Long history (again removing based on delta-time)– Does not effect to vectors stored by ”alarm” or ”user” or from TG run-up/coasts-down
stage (these have their own history piles
Adaptive alarm limit handling application (”IAH)
What it means
”Standard” alarm limit handling has been to use fixed warning (H or L) and
alarm (HH or LL) limits for vibration values
Adaptive handling brings the possibility to adapt alarm limits into changes in
operating conditions, typically;– Machine speed (m/min) / rotating frequency (Hz)– Machine load
A separate application to tune the limits after system /machine / productions
star