HE693RTD600
The HE693RTD600 allows RTD temperature sensors to be connected to the PLC directly without external signal processing such as transducers, transmitters, etc.
All analog and digital processing on the module is performed on the HE693RTD600.
and temperature values in 0.5°C or 0.5°F increments are written to the 90-30 %AI input table.
All modules feature six channels, and support PT-90 (MIL-7990), PT-100 (alpha=.00385. . 003902 and . 03906), Ni-120. Cu-10. Cu-50. Cu-53. Cu-100. Pt-1000. TD5R and Linear Resistance.
Technical Specifications
Power Consumption (Typical) 75mA @ 5VDC
Number of Channels 6
I/O Points Required 6%AI
Input Impedance >1000 Meg Ω
Fault Protection Zener Diode Clamp
A/D Conversion Type 16 bit, Integrating
Update Time 50 Channels per second
Average RTD current, PT-100 330 microamps
Channel to Channel Tracking 0.1°C
Resolution 0.1°C
Accuracy ± 0.5°C typical, ± 1.0°C for Cu-10 and TD5R
Operating Temperature 0 to 60°C (32° to 140°F)
Relative Humidity 5% to 95% non-condensing